| 2014-10-10 15:26:19 | 10/10/2014 | | | PROJECT: GRAND ILLUSIONS | | | PERMIT#: 14081208 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | ELECTRICAL PLAN REVIEW | | | ACTION: PROVISO | | | | | | 1) NEC 430.102 LOCATION. | | | AN INDIVIDUAL DISCONNECTING MEANS SHALL BE PROVIDED FOR | | | EACH CONTROLLER AND SHALL DISCONNECT THE CONTROLLER. | | | THE DISCONNECTING MEANS SHALL BE LOCATED IN SIGHT FROM | | | THE CONTROLLER LOCATION | | | | | | 2) SEPARATE ELECTRICAL PERMIT APPLICATIONS IS REQUIRED | | | FOR INSTALLATION OF ELECTRICAL | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | | SHEETS FOR COMPARATIVE REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|