| 2014-09-19 15:26:02 | BUILDING PLAN REVIEW |
| | PERMIT: 14081188 |
| | ADD: 1845 PALM BEACH LAKES TEMP. MAN BLDG. |
| | CONT: MCINTYRE ELWELL & STRAMMER |
| | TEL: (561) 401-1349 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: FRI. SEPT. 19/2014 |
| | ACTION: BUILDING PROVISO |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | |
| | 1) THIS MANUFACTURERED BUILDING APPEARS TO HAVE BEEN |
| | BUILT UNDER THE 1997 SBC WITH WIND SPEED OF 110 MPH |
| | FASTEST MILE. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 102.7 RELOCATION OF |
| | MANUFACTURED BUILDINGS. 2.2. A RELOCATED BUILDING SHALL |
| | COMPLY WITH WIND SPEED REQUIREMENTS OF THE NEW |
| | LOCATION, USING THE |
| | APPROPRIATE WIND SPEED MAP. IF THE EXISTING BUILDING |
| | WAS MANUFACTURED IN COMPLIANCE WITH THE |
| | STANDARD BUILDING CODE (PRIOR TO MARCH 1, 2002), THE |
| | WIND SPEED MAP OF THE STANDARD BUILDING |
| | CODE SHALL BE APPLICABLE. IF THE EXISTING BUILDING WAS |
| | MANUFACTURED IN COMPLIANCE WITH THE |
| | FLORIDA BUILDING CODE (AFTER MARCH 1, 2002), THE WIND |
| | SPEED MAP OF THE FLORIDA BUILDING CODE |
| | SHALL BE APPLICABLE.. IF THE EXISTING BUILDING WAS |
| | MANUFACTURED IN COMPLIANCE WITH THE STANDARD BUILDING |
| | CODE (PRIOR TO MARCH 1, 2002), THE WIND SPEED MAP OF |
| | THE STANDARD BUILDING CODE SHALL BE APPLICABLE. IF THE |
| | EXISTING BUILDING WAS MANUFACTURED IN COMPLIANCE WITH |
| | THE FLORIDA BUILDING CODE (AFTER MARCH 1, 2002), THE |
| | WIND SPEED MAP OF THE FLORIDA BUILDING CODE SHALL BE |
| | APPLICABLE. |
| | |
| | THE 2010 FL BUILDING CODE WIND DESIGN IS 170MPH VULT |
| | WHICH EQUALS 132 VASD. WHEN THE 110 MPH FASTESTMILE IS |
| | CONVERTED INTO VASD IT EQUALS 130 MPH. IF YOU |
| | INTERPALATE THE 132 MPH VASD FOR THIS LOCATION IT WOULD |
| | BE 130 MPH. SO THE STRUCTURE WILL WITHSTAND THE |
| | PRESSURES. |
| | |
| | THE ADMINISTRATIVE CODE SECTION 107.2 2. A RELOCATED |
| | BUILDING SHALL COMPLY WITH WIND SPEED REQUIREMENTS OF |
| | THE NEW LOCATION, USING THE |
| | APPROPRIATE WIND SPEED MAP. THIS REGION IS A WIND |
| | -BORNE DEBRIS REGION THAT WILL REQUIRE STORM SHUTTERS |
| | SEE 2010 FBC-B 1609.1.2 SINCE THE GLAZING IS NOT LARGE |
| | MISSILE RESISTANT TESTED. STORM SHUTTERS WILL BE |
| | REQUIRED UNDER A SEPARATE PERMIT. |
| | |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |