| 2014-09-02 13:43:35 | BUILDING PLAN REVIEW |
| | PERMIT: 14081186 |
| | ADD: 1845 PALM BEACH LAKES (MANUFACTURED BLDG) |
| | CONT: MCINTYRE & ELWELL & STRAMMER GC, INC. |
| | TEL: (941)377-6800 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. SEPT. 01/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) THE COVERSHEET INDICATES THE VULT 165 MPH, PLEASE |
| | SHOW HOW THROUGH INTERPOLATION THE 165 MPH WAS ARRIVED. |
| | THE WIND SPEED MAP |
| | SEE FIGURE 1609A. |
| | |
| | 2) THE MODULAR BUILDING NO LONGER HAS A STATE APPROVED |
| | PLANS, HOW WILL THE INSPECTIONS TAKE PLACE FOR A |
| | BUILDING THAT IS ALREADY FINISHED. |
| | 2010 FBC-EXISTING BUILDING CODE1202.7 REQUIRED |
| | INSPECTION AND REPAIRS. |
| | THE CODE OFFICIAL SHALL BE AUTHORIZED TO INSPECT, OR TO |
| | REQUIRE APPROVED PROFESSIONALS TO INSPECT AT THE |
| | EXPENSE OF THE OWNER, THE VARIOUS STRUCTURAL PARTS OF A |
| | RELOCATED BUILDING TO VERIFY THAT STRUCTURAL COMPONENTS |
| | AND CONNECTIONS HAVE NOT SUSTAINED STRUCTURAL DAMAGE. |
| | ANY REPAIRS REQUIRED BY THE CODE OFFICIAL AS A RESULT |
| | OF SUCH INSPECTION SHALL BE MADE PRIOR TO THE FINAL |
| | APPROVAL. |
| | |
| | 3) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |