| Plan Review Notes For Permit 14081149 |
| Permit Number |
14081149 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-08-27 12:31:45 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 | | | [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2010 | | | | | | TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED | | | | | | 1. THE IIC REPORT INCLUDES A DROPPED CEILING. THE STC | | | REPORT WAS NOT PROVIDED. | | | | | | PLEASE REVISE PLAN - DOES THE SPACE (UNIT) BELOW THE | | | RENOVATED AREA HAVE A DROPPED CEILING IN THIS AREA? IF | | | IT DOES, REVISE PLAN TO INDICATE THAT THERE IS A | | | DROPPED CEILING BELOW. ALSO SUBMIT THE STC TEST REPORT, | | | FBC 1207.2. | | | | | | IF THE UNIT BELOW DOES NOT HAVE A DROPPED CEILING, PER | | | MANUFACTURER THIS PRODUCT (MSC90) DOES NOT MEET THE | | | MINIMUM RATING OF 50 WITHOUT THE DROPPED CEILING. | | | MANUFACTURER OF PROFLEX RECOMMENDED RCU250 IF THERE IS | | | NO DROPPED CEILING BELOW. | | | |
|