| 2014-08-28 11:55:58 | BUILDING PLAN REVIEW |
| | PERMIT: 14081143 |
| | ADD: 303 BANYAN BLVD |
| | CONT: IBIS BUILDING |
| | TEL: (561)318-3408 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. AUG. 28/2014 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A1.1 VERSES THE STRUCTURAL SHEETS. THE PLANS |
| | ARE NOT CLEAR TO THE BACK 1/3RD OF THE TENANT SUITE IF |
| | THE CONCRETE FLOOR IS BEING REMOVED OR IS THE STEEL |
| | FRAMING BELOW BEING REPLACED? THERE IS NO NOTE ON THE |
| | A1.1 UNDER THE DEMO NOTES THIS FLOOR IS BEING REMOVED. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2.1.3. ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 2) SHEET A1.1 LIST THE COMMON PATH OF TRAVEL FROM THE |
| | BACK CORNER OF THE RESTROOM TO THE FRONT ENTRY 107 FT. |
| | THAT EXCEEDS THE COMMON PATH OF TRAVEL EXCEPTION # 1 OF |
| | 1014.3 OF 100 FT. WOULDN'T THE COMMON PATH OF TRAVEL |
| | STOP AT THE REAR EXIT. |
| | |
| | 3) OFFICE # 104 THE INSWING DOOR DOES NOT HAVE THE |
| | REQUIRED 18 INCHES LATCH SIDE OF DOOR. 2010 |
| | FBC-ACCESSIBILITY CODE 404.2.4.1 AND TABLE 404.2.4.1. |
| | |
| | 4A) A1.1 SHOWS A 2HR RATED STAIR ENCLOSURE, SHEET A.2.1 |
| | SHOWS A WALL INFILL, WALL IDENTIFICATION TAG W3. PLEASE |
| | REVIEW SHEET A3.1 WALL TYPES. THE WRITTEN WORD DOES NOT |
| | LINE UP WITH THE DETAILS, NOT SURE WHICH DETAIL TIES TO |
| | WHICH WALL TYPE. DISCREPANCY IN PLANS. 107.2.1.3. |
| | |
| | 4B) SHEET A3.1 WALL IDENTIFICATION TAGS, 2 WALL TYPES |
| | INDICATE A UL DESIN NUMBER, U419 & U465. NEITHER |
| | PROVIDE A DETAIL OF THESE ASSEMBLIES. NOTE U-419 CAN BE |
| | 1-4 HOUR RATING, WHICH ARE YOU DESIGNING TOO? |
| | |
| | 4C) SHEET A2.1, A3.1 AND S-1 DISCREPANCY IN PLANS. THE |
| | INFILL WALL OF THE 2 HR RATED EXIT ENCLOSRE ON THE |
| | SHEET S-1 INDICATES THE USE OF 8 INCH CMU. 107.2.1.3 |
| | DISCREPANCY IN PLANS, ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 5) SHEET S-2 INDICATES TH USE OF 20 GAUGE STUDS, IN 20 |
| | GAUGE STUDS THERE ARE (2) THICKNESSES, PLEASE SPECIFY, |
| | DRYWALL 30(MILS) AND STRUCTURAL 33(MILS)? |
| | |
| | 6) SHEET A 2.1 & A4.1 BOTH INDICATE A NEW EXTERIOR |
| | DOOR, PLEASE PROVIDE COMPLIANCE WITH: 2010 FBC-B |
| | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS |
| | & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | |
| | |
| | 7) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |