2014-09-16 16:48:416651 NORTH JOG ROAD - POWER BLOCK
 PERMIT #14081134
 MASTER #12040748
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVISO - SUBMIT REVISION
  
 SMALL HOSE CONNECTIONS: SEVERAL BUILDING AREAS,
 INCLUDING THIS SUBMITTAL FOR THE WATER TREATMENT
 BUILDING AND TURBINE BUILDING ARE SHOWING SMALL HOSE
 CONNECTIONS OF 1-1/2"; HOWEVER, THE HOSE VALVES HAVE
 PRESSURES THAT WILL EXCEED 100 PSI AS THE PRESSURE IS
 INDICATED AS 140 PSI RESIDUAL AT THE BUILDING RISER.
 NFPA 13 AND NFPA 14 SEEM TO AGREE, WHERE THE RESIDUAL
 PRESSURE AT A 1-1/2" OUTLET ON A HOSE CONNECTION
 AVAILABLE FOR TRAINED PERSONNEL USE EXCEEDS 100 PSI, AN
 APPROVED PRESSURE-REGULATING DEVICE SHALL BE PROVIDED
 TO LIMIT THE RESIDUAL PRESSURE TO 100 PSI. THE HOSE AND
 REEL WILL NEED TO BE ELIMINATED BECAUSE FIRE DEPARTMENT
 PERSONNEL WILL NOT USE THIS EQUIPMENT AND CIVILIANS MAY
 BE TEMPTED TO UTILIZE THE HOSE IF IT IS READILY
 AVAILABLE. THIS APPLIES THROUGHOUT THE CAMPUS. SWA
 EMPLOYEES ARE NOT TRAINED IN PROPER FIRE-FIGHTING
 TECHNIQUES AND ARE EXPECTED TO EVACUATE THE BUILDING IN
 A FIRE EVENT.
  
 THESE COMMENTS ARE VEY SIMILAR TO THE COMMENTS PROVIDED
 FOR PERMIT #13100958.
  