| 2014-09-16 16:48:41 | 6651 NORTH JOG ROAD - POWER BLOCK |
| | PERMIT #14081134 |
| | MASTER #12040748 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | PROVISO - SUBMIT REVISION |
| | |
| | SMALL HOSE CONNECTIONS: SEVERAL BUILDING AREAS, |
| | INCLUDING THIS SUBMITTAL FOR THE WATER TREATMENT |
| | BUILDING AND TURBINE BUILDING ARE SHOWING SMALL HOSE |
| | CONNECTIONS OF 1-1/2"; HOWEVER, THE HOSE VALVES HAVE |
| | PRESSURES THAT WILL EXCEED 100 PSI AS THE PRESSURE IS |
| | INDICATED AS 140 PSI RESIDUAL AT THE BUILDING RISER. |
| | NFPA 13 AND NFPA 14 SEEM TO AGREE, WHERE THE RESIDUAL |
| | PRESSURE AT A 1-1/2" OUTLET ON A HOSE CONNECTION |
| | AVAILABLE FOR TRAINED PERSONNEL USE EXCEEDS 100 PSI, AN |
| | APPROVED PRESSURE-REGULATING DEVICE SHALL BE PROVIDED |
| | TO LIMIT THE RESIDUAL PRESSURE TO 100 PSI. THE HOSE AND |
| | REEL WILL NEED TO BE ELIMINATED BECAUSE FIRE DEPARTMENT |
| | PERSONNEL WILL NOT USE THIS EQUIPMENT AND CIVILIANS MAY |
| | BE TEMPTED TO UTILIZE THE HOSE IF IT IS READILY |
| | AVAILABLE. THIS APPLIES THROUGHOUT THE CAMPUS. SWA |
| | EMPLOYEES ARE NOT TRAINED IN PROPER FIRE-FIGHTING |
| | TECHNIQUES AND ARE EXPECTED TO EVACUATE THE BUILDING IN |
| | A FIRE EVENT. |
| | |
| | THESE COMMENTS ARE VEY SIMILAR TO THE COMMENTS PROVIDED |
| | FOR PERMIT #13100958. |
| | |