| Plan Review Notes For Permit 14081130 |
| Permit Number |
14081130 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-09-12 15:13:41 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | SHOWING THE MAIN DOUBLE DOOR SWINGING INTO THE HALL, IN | | | THE DIRECTION OF TRAVEL TO USE THE DEVICES, IT THEN | | | MUST/SHALL MEET THE REQUIREMENTS OF NFPA 101, 2010 ED. | | | | | | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS | | | OF EGRESS SHALL NOT LEAVE LESS THAN ONE-HALF OF THE | | | REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, | | | OR A LANDING UNOBSTRUCTED AND SHALL PROJECT NOT MORE | | | THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A | | | CORRIDOR, A PASSAGEWAY, OR A LANDING, WHEN FULLY | | | OPEN.....REMAINDER OF CODE CONDITIONS DO NOT APPLY. | | | | | | DIMENSIONS OF THE HALLWAY AND DOOR ARE NOT PROVIDED; | | | HOWEVER, IF DRAWN TO SCALE IT MAY PROVDE ENOUGH ROOM. | | | FINAL APPROVAL, IF INSTALLED, IS CONTINGENT ON REVEIW | | | AND VERIFICATION BY A FIRE INSPECTOR. INSPECTION WILL | | | FAIL IF THE INSTALLATION DOES NOT MEET THE | | | REQUIREMENTS. | | | | | | |
|