| Plan Review Notes For Permit 14081130 |
| Permit Number |
14081130 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-08-28 12:32:08 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | THE DOUBLE ENTRY DOOR SWING EGRESS DOES NOT MEET # 3 OF | | | THE REQUIREMENTS OF 7.2.1.6.2. | | | | | | (3) THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE | | | DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE | | | LOCATED (40IN TO 48IN) VERTICALLY ABOVE THE FLOOR AND | | | WITHIN (60IN) OF THE SECURED DOORS. | | | | | | THE DOORS AS SHOWN OPEN AGAINST EGRESS. |
|