| Plan Review Notes For Permit 14081123 |
| Permit Number |
14081123 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-06 11:04:27 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. SCOPE OF WORK NOT CLEAR, FBC 107. APPLICATION STATES | | | THAT TWO WINDOWS AND ONE DOOR WILL BE INSTALLED. PLAN | | | AND SCHEDULE SHOW TWO OPENINGS, NOT THREE, AND DOES NOT | | | DESIGNATE WHAT WILL BE INSTALLED IN WHICH LOCATION. | | | SINCE A MULLION PRODUCT APPROVAL IT APPEARS THAT TWO | | | WINDOWS MAY BE INSTALLED IN ONE OPENING, BUT THE SIZE | | | IS SHOWN AS 53 X 72. IS THAT OVERALL OR FOR EACH | | | WINDOW? IF IT'S OVERALL, THAT REDUCES THE CLEAR | | | OPENING, WHAT IS THE ROOM DESIGNATION? SEE FBC FBC | | | R310, FBC EB 604.1. THE CLEAR OPENING CANNOT BE REDUCED | | | BY MORE THAN 5%. | | | | | | REVISE PLAN TO BE CLEAR AS TO PROPOSED INSTALLATION. | | | INCLUDE ROOM DESIGNATIONS. | | | | | | 2. TWO SETS REQUIRED FOR PERMIT ISSUANCE, FBC 107. ONLY | | | ONE FLOOR PLAN WAS SUBMITTED. | | | |
|