2014-12-23 07:58:23RESIDENTIAL (R3) ADDITION, SECOND MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE EQUIPMENT SIZING CALCULATIONS FOR ENTIRE
 HOUSE INCLUDING THE PROPOSED ADDITION. CALCULATIONS
 SUBMITTED ARE ONLY FOR THE ADDITION AND DON'T SHOW THE
 EXISTING EQUIPMENT SPECIFICATIONS. UNABLE TO VERIFY IF
 THE EXISTING EQUIPMENT IS ADEQUATE FOR THE ADDITIONAL
 LOAD. PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS
 SHOWING ALL THE EXISTING EQUIPMENT SPECS. INFORMATION
 LIKE "GENERIC" IS NOT ACCEPTABLE TO SHOW COMPLIANCE.
 SEC. 107.3.5.3 (10) OF CITY AMENDMENTS TO FBC.
  
 REPEAT COMMENT. CALCULATIONS SUBMITTED DON'T PROVIDE
 ENOUGH INFORMATION TO REVIEW IF THE EQUIPMENT IS
 PROPERLY SIZED FOR THE EXISTING HOUSE AND PROPOSED
 ADDITION. THERE ARE NOT SPECS FOR THE EQUIPMENT. THERE
 IS NO INFORMATION IF THE EQUIPMENT IS EXISTING OR NEW.
 PLEASE PROVIDE COMPLETE INFORMATION TO AVOID DELAYS OR
 CONFLICTS.
  