| 2014-12-23 07:58:23 | RESIDENTIAL (R3) ADDITION, SECOND MECHANICAL REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- PROVIDE EQUIPMENT SIZING CALCULATIONS FOR ENTIRE | | | HOUSE INCLUDING THE PROPOSED ADDITION. CALCULATIONS | | | SUBMITTED ARE ONLY FOR THE ADDITION AND DON'T SHOW THE | | | EXISTING EQUIPMENT SPECIFICATIONS. UNABLE TO VERIFY IF | | | THE EXISTING EQUIPMENT IS ADEQUATE FOR THE ADDITIONAL | | | LOAD. PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS | | | SHOWING ALL THE EXISTING EQUIPMENT SPECS. INFORMATION | | | LIKE "GENERIC" IS NOT ACCEPTABLE TO SHOW COMPLIANCE. | | | SEC. 107.3.5.3 (10) OF CITY AMENDMENTS TO FBC. | | | | | | REPEAT COMMENT. CALCULATIONS SUBMITTED DON'T PROVIDE | | | ENOUGH INFORMATION TO REVIEW IF THE EQUIPMENT IS | | | PROPERLY SIZED FOR THE EXISTING HOUSE AND PROPOSED | | | ADDITION. THERE ARE NOT SPECS FOR THE EQUIPMENT. THERE | | | IS NO INFORMATION IF THE EQUIPMENT IS EXISTING OR NEW. | | | PLEASE PROVIDE COMPLETE INFORMATION TO AVOID DELAYS OR | | | CONFLICTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|