| 2014-10-01 10:23:33 | RESIDENTIAL (R3) ADDITION, MECHANICAL REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- SHEET 7: PROVIDE THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE A/C DESIGN AS REQUIRED BY | | | SEC. 107.2.1 OF CITY AMENDMENTS TO FBC. | | | | | | 2- PROVIDE EQUIPMENT SIZING CALCULATIONS FOR ENTIRE | | | HOUSE INCLUDING THE PROPOSED ADDITION. CALCULATIONS | | | SUBMITTED ARE ONLY FOR THE ADDITION AND DON'T SHOW THE | | | EXISTING EQUIPMENT SPECIFICATIONS. UNABLE TO VERIFY IF | | | THE EXISTING EQUIPMENT IS ADEQUATE FOR THE ADDITIONAL | | | LOAD. PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS | | | SHOWING ALL THE EXISTING EQUIPMENT SPECS. INFORMATION | | | LIKE "GENERIC" IS NOT ACCEPTABLE TO SHOW COMPLIANCE. | | | SEC. 107.3.5.3 (10) OF CITY AMENDMENTS TO FBC. | | | | | | ***NOTE: SURVEY AND SITE PLAN ON SHEET 1 SHOW THAT THE | | | CONDENSER UNIT IS ENCROACHING INTO THE NEIGHBOR'S | | | PROPERTY. SEE ZONING COMMENTS AND RESPPOND TO THIS | | | ISSUE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|