2014-10-01 10:23:33RESIDENTIAL (R3) ADDITION, MECHANICAL REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- SHEET 7: PROVIDE THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE A/C DESIGN AS REQUIRED BY
 SEC. 107.2.1 OF CITY AMENDMENTS TO FBC.
  
 2- PROVIDE EQUIPMENT SIZING CALCULATIONS FOR ENTIRE
 HOUSE INCLUDING THE PROPOSED ADDITION. CALCULATIONS
 SUBMITTED ARE ONLY FOR THE ADDITION AND DON'T SHOW THE
 EXISTING EQUIPMENT SPECIFICATIONS. UNABLE TO VERIFY IF
 THE EXISTING EQUIPMENT IS ADEQUATE FOR THE ADDITIONAL
 LOAD. PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS
 SHOWING ALL THE EXISTING EQUIPMENT SPECS. INFORMATION
 LIKE "GENERIC" IS NOT ACCEPTABLE TO SHOW COMPLIANCE.
 SEC. 107.3.5.3 (10) OF CITY AMENDMENTS TO FBC.
  
 ***NOTE: SURVEY AND SITE PLAN ON SHEET 1 SHOW THAT THE
 CONDENSER UNIT IS ENCROACHING INTO THE NEIGHBOR'S
 PROPERTY. SEE ZONING COMMENTS AND RESPPOND TO THIS
 ISSUE.
  