| Plan Review Notes For Permit 14081090 |
| Permit Number |
14081090 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-04 12:26:11 | 1ST REVIEW: FBC 2010; NEC 2008 | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO | | | FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS. | | | | | | FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 | | | FEET OF EACH SLEEPING ROOM. | | | | | | NEC 210.52(A)(1)&(2) OUTLET SPACING, IT APPEARS SOME | | | POINTS ALONG THE WALL EXCEED 6? FROM AN OUTLET | | | | | | N.E.C. 250.104 (3)B BOND OTHER METAL PIPING,GAS PIPING | | | AT TANKLESS WATER HEATER. | | | | | | STEPHEN CIARDIELLO, | | | CHIEF ELECTRICAL INSPECTOR | | | (561) 805-6743 | | | [email protected] | | | | | | |
|