2014-09-19 14:52:34DATE: 9/19/2014
 PROJECT: PALM BEACH LAKES MALL BUILDING H
 PERMIT#: 14081077 MASTER PERMIT#13120923
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE
 THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES. THE BRANCH CIRCUIT THAT FEEDS UNIT EQUIPMENT
 SHALL BE CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL.
 EMERGENCY LUMINAIRES THAT OBTAIN POWER FROM A UNIT
 EQUIPMENT AND ARE NOT PART OF THE UNIT EQUIPMENT SHALL
 BE WIRED TO THE UNIT EQUIPMENT AS REQUIRED BY 700.9 AND
 BY ONE OF THE WIRING METHODS OF CHAPTER 3. NEC
 700.12(F)
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  