| 2014-08-27 15:25:15 | BUILDING PLAN REVIEW |
| | PERMIT: 14081026 |
| | ADD: 222 LAKEVIEW AVE. |
| | CONT: FASTRACK |
| | TEL: (561)304-7881 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: WED. AUG. 27/2014 |
| | ACTION: PASSED. |
| | |
| | 1) THIS IS A HIGHRISE BUILDING, THE 2010 FBC-B 708.14.1 |
| | REQUIRES ELEVATOR LOBBIES EVEN IF THIS PORTION OF THE |
| | BUILDING IS ONLY 5 STORIES TALL OR MEET ONE OF THE |
| | SEVEN EXCEPTIONS, THIS IS CONSIDERED NEW WORK. 2010 |
| | EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. THE M3 SHEET |
| | DOES SHOW SF-1 FAN PRESSURIZING THE ELEVATOR SHAFTWAY. |
| | THE SHEET M2 NOTE2 ONCE THE SMOKE ALARM CLOSES VANT # |
| | 1, THE VENTS LABELED # 2 WILL OPEN ON ACTUATION OF |
| | SMOKE ALARM OTHERWISE THEY ARE SET AND OPERATE AS A |
| | BAROMETER PRESSURE SENSOR. |
| | |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |