| Date |
Text |
| 2014-08-27 11:04:12 | BUILDING PLAN REVIEW |
| | PERMIT: 14081026 |
| | ADD: 222 LAKEVIEW AVE. |
| | CONT: FASTRACK |
| | TEL: (561)304-7881 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: WED. AUG. 27/2014 |
| | ACTION: DENIED |
| | |
| | 1) THIS IS A HIGHRISE BUILDING, THE 2010 FBC-B 708.14.1 |
| | REQUIRES ELEVATOR LOBBIES EVEN IF THIS PORTION OF THE |
| | BUILDING IS ONLY 5 STORIES TALL OR MEET ONE OF THE |
| | SEVEN EXCEPTIONS, THIS IS CONSIDERED NEW WORK. 2010 |
| | EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. THE M3 SHEET |
| | DOES SHOW SF-1 FAN PRESSURIZING THE ELEVATOR SHAFTWAY. |
| | THE SHEET M2 NOTE2 ONCE THE SMOKE ALARM CLOSES VANT # |
| | 1, THE VENTS LABELED # 2 WILL OPEN ON ACTUATION OF |
| | SMOKE ALARM OTHERWISE THEY ARE SET AND OPERATE AS A |
| | BAROMETER PRESSURE SENSOR. |
| | |
| | 2) THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " |
| | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 2A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A |
| | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| | A THRESHOLD BUILDING PURSUANT TO A WRITTEN STRUCTURAL |
| | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE |
| | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE |
| | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| | COMPLIANCE WITH THE PERMITTED DOCUMENTS. 3 SETS OF |
| | DOCUMENTS WILL BE REQUIRED. |
| | |
| | 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. THRESHOLD INSPECTOR FORM WILL BE |
| | REQUIRED TO BE FILED OUT BEFORE PERMIT ISSUANCE CAN |
| | OCCUR. CONTACT KEN CONRAD MANAGER OF THE SPECIAL |
| | INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER |
| | INFORMATION. |
| | |
| | 2C) THRESHOLD BLDG, REQUIRED STATEMENT: |
| | W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING |
| | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| | LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE. |
| | |
| | 2D) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN |
| | CONRAD: [email protected] |
| | |
| | 2E) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 2F) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| | FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| | HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| | MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| | WALLS AND CEILINGS. |
| | |
| | 2G) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| | IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS. |
| | |
| | 3) THE BUILDING SHEETS A3.2 AND MECHANICAL SHEETS M.2 |
| | BOTH INDICATE REQUIREMENTS FOR PRODUCT APPROVALS TO BE |
| | SUBMITTED. |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| | COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | RULE 9N-3(31)(C) WALL LOUVERS |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | |
| | 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 5) NEITHER THE ARCHITECTURAL NOR STRUCTURAL SHEETS |
| | PROVIDE THE WIND DESIGN CRITERIA FOR THE NEW ELEVATOR |
| | PENTHOUSE ROOM NOR LOUVERS ONTHE NEW PENTHOUSE. 2010 |
| | FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- CHAPTER 6 |
| | OF ASCE 7-10. |
| | |
| | 6) SHEET A3.2 DETAIL # A1 SHOWS THIS ELEVATOR TO USE A |
| | HYDROLIC ELEVATOR, PLEASE PROVIDE CODE COMPLIANCE WITH |
| | 3011.1(1-4) ELECTROLYSIS PROTECTION FOR UNDERGROUND |
| | HYDRAULIC ELEVATOR CYLINDERS. ALL NEWLY INSTALLED |
| | UNDERGROUND HYDRAULIC PRESSURE CYLINDERS SHALL BE |
| | ENCASED IN OUTER PLASTIC CONTAINMENT TO MINIMIZE |
| | ELECTROLYTIC CORROSION BETWEEN THE METAL CYLINDER AND |
| | GROUND CATHODE. |
| | |
| | 7) SHEET M3 SHOWS A NEW ROOF TOP CURB FOR NEITHER THE |
| | STRUCTURAL SHEETS NOR MECHANICAL SHEETS SHOW THE METHOD |
| | OF ATTACHMENT OF THE CURB TO THE STRUCTURAL ROOF NOR |
| | THE FAN TO THE CURB. 2010 FBC-B 1609.1.2 PROTECTION OF |
| | OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | : WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |