2014-09-09 11:28:04DATE: 9/9/2014
 PROJECT: GENERATOR
 PERMIT#: 14081009
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) THE ELECTRICAL RESER DIAGRAM INDICATES TWO SEPARATE
 200AMP SERVICE ENTRANCE FEEDERS TO TO SEPARATE 200 AMP
 PANELS. NEC 310.16 CALLS FOR A MINIMUM 3/0CU FEEDER FOR
 200AMP.
 NEC 310.15(B)(6) IS ONLY FOR A SINGLE SERVICE ENTRANCE.
 REVISE PLAN TO INDICATE FULL SIZE SERVICE ENTRANCE
 CONDUCTOR SETS.
  
 2) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS
 TO FBC 107.2.1.
 REVISE THE PLANS WITH THE SIGNATURE OF THE QUALIFIER OR
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  