| 2014-09-09 11:28:04 | DATE: 9/9/2014 |
| | PROJECT: GENERATOR |
| | PERMIT#: 14081009 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) THE ELECTRICAL RESER DIAGRAM INDICATES TWO SEPARATE |
| | 200AMP SERVICE ENTRANCE FEEDERS TO TO SEPARATE 200 AMP |
| | PANELS. NEC 310.16 CALLS FOR A MINIMUM 3/0CU FEEDER FOR |
| | 200AMP. |
| | NEC 310.15(B)(6) IS ONLY FOR A SINGLE SERVICE ENTRANCE. |
| | REVISE PLAN TO INDICATE FULL SIZE SERVICE ENTRANCE |
| | CONDUCTOR SETS. |
| | |
| | 2) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS |
| | TO FBC 107.2.1. |
| | REVISE THE PLANS WITH THE SIGNATURE OF THE QUALIFIER OR |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |