| 2014-09-09 18:24:44 | DECK REPLACEMENT, BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- ENGINEER OF RECORD TO SPECIFY CURRENT BUILDING CODE |
| | AND ALL THE DESIGN LOADS AS REQUIRED BY SEC. 1603.1 AND |
| | TABLE 1607.1 OF 2010 FBC. |
| | |
| | 2- A) PROVIDE PRODUCT APPROVAL OR ICC EVALUATION REPORT |
| | (2 COPIES) AS REQUIRED BY DCA RULE 9N-3 FOR THE |
| | MANUFACTURED COMPOSITE DECK TO BE INSTALLED. |
| | |
| | B) ENGINEER TO REVIEW THE LIMITATIONS ON THE ICC |
| | EVALUATION REPORT TO VERIFY THAT LOADS REQUIRED BY ITEM |
| | #1 ABOVE ARE MET. FOR EXAMPLE VERIFY THAT THE MAXIMUM |
| | MEMBER SPAN BETWEEN SUPPORTS IS 24" AS SPECIFIED ON |
| | PLANS SUBMITTED. OTHERWISE, REVISE PLANS AS REQUIRED. |
| | SEC. 107.2.1.3 CITY AMENDMENTS TO FBC. |
| | |
| | 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| | REINSTALLING OF THE EXISTING RAILING SYSTEM TO SHOW |
| | COMPLIANCE WITH SEC. 1607.7 OF 2010 FBC. |
| | |
| | 4- CLEARLY SPECIFY SPECIFIC SIMPSON STRAPS TO BE USED |
| | IN DETAILS 1/S-1, 2/S-1. SEC. 107.2.1.3 CITY AMENDMENTS |
| | TO FBC. |
| | |
| | 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. PROPOSED DECKING IS MORE EXPENSIVE THAN |
| | CONVENTIONAL WOOD PRODUCTS. PROVIDE TOTAL SQUARE |
| | FOOTAGE AREA TO BE REPLACED AND UPDATE VALUATION AS |
| | REQUIRED. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| | CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN |
| | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| | AMENDMENTS TO FBC. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |