| Plan Review Notes For Permit 14080992 |
| Permit Number |
14080992 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-09 12:48:35 | 14080992 | | | 1301 SUMMIT BLVD. | | | SOLAR ENERGY SYSTEM | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | FEEDERS TO THE NEW 100 AMPERE PANEL ARE UNDERSIZED. NEC | | | 240.21 | | | | | | PROVIDE NOTE ON PLANS THAT PVC CONDUIT WHERE EXPOSED TO | | | PHYSICAL DAMAGE SHALL BE IDENTIFIED FOR THE USE (SUCH | | | AS TYPE SCHEDULE 80). | | | | | | INDICATE THAT ALL REQUIRED PV SAFETY LABELLING AND | | | SIGNAGE MUST BE SUITABLE FOR THE ENVIRONMENT AND | | | PERMANENT IN NATURE. NEC 705.10 | | | | | | ROBERT LECKY, CBO | | | ELECTRICAL PLANS REVIEW | | | 561-373-3701 | | | [email protected] | | | |
|