Plan Review Notes
Plan Review Notes For Permit 14080992
Permit Number 14080992
Review Stop E
Sequence Number 1
Notes
Date Text
2014-09-09 12:48:3514080992
 1301 SUMMIT BLVD.
 SOLAR ENERGY SYSTEM
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 FEEDERS TO THE NEW 100 AMPERE PANEL ARE UNDERSIZED. NEC
 240.21
  
 PROVIDE NOTE ON PLANS THAT PVC CONDUIT WHERE EXPOSED TO
 PHYSICAL DAMAGE SHALL BE IDENTIFIED FOR THE USE (SUCH
 AS TYPE SCHEDULE 80).
  
 INDICATE THAT ALL REQUIRED PV SAFETY LABELLING AND
 SIGNAGE MUST BE SUITABLE FOR THE ENVIRONMENT AND
 PERMANENT IN NATURE. NEC 705.10
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW