2014-09-18 11:10:36DATE: 9/18/2014
 PROJECT: MALONE
 PERMIT#: 14080991
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1)THE RISER DIAGRAM SUBMITTED INDICATES THE LOAD BEING
 FED FROM THE PHASE GENERATOR/MOTOR. THE MANUFACTURER
 DATA SHEETS SUBMITTED INDICATE THE LOAD BEING FED FROM
 THE PHASE CONVERTER. REVISE THE PLANS TO COINCIDE WITH
 THE MANUFACTURER DATA SHEETS PROVIDED AND THE NEC.
  
 2) ACCORDING TO THE MANUFACTURER DATA SHEETS PROVIDED,
 THE MINIMUM WIRE SIZE TO THE PHASE GENERATOR/MOTOR IS A
 1/0 AND THE PLAN INDICATES THE USE OF A #2. REVISE
 PLANS TO COINCIDE WITH THE MANUFACTURER DATA SHEETS
 PROVIDED AND THE NEC 430
  
 3) PROVIDE A LOAD CALCULATION FOR BOTH THE SINGLE PHASE
 AND 3 PHASE LOADS TO BE SERVED. INCLUDE IN THE SINGLE
 PHASE CALCULATION THE TOTAL CONNECTED LOAD OF THE
 BUILDING PLUS THE PROPOSED 3 PHASE CALCULATED LOAD.
 NEC215.5
  
 4) PROVIDE 3PHASE DISCONNECT AHEAD OF 3PHASE LOAD SIZED
 APPROPRIATELY TO PROTECT THE WIRE SIZE REQUIRED BASED
 ON THE TOTAL CALCULATED LOAD. NEC 430, 310.16
  
 5) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. PROVIDE A FAULT CURRENT CALCULATION. NEC
 110.9
  
 6) THE #2/0 CU FEEDING THE PHASE CONVERTER FROM 200AMP
 MAIN 2 0F 2 IS UNDERSIZED FOR THE 200AMP MAIN. THE #8
 CU GRD WIRE IS UNDERSIZED FOR THE 200AMP MAIN. NEC
 310.16, 250.122
  
 7) PROVIDE THE LISTING ON THE PROPOSED NEW EQUIPMENT
 FROM AN APPROVED NATIONALLY RECOGNIZED TESTING
 LABORATORY. NEC 110.3
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  