| Plan Review Notes For Permit 14080956 |
| Permit Number |
14080956 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-25 09:05:38 | | | | AREAS NOT ADDRESSED IN THESE PLANS ARE ENERGY, MAKE UP | | | AIR (PHARMACY). | | | INDICATED ON THE SCHEDULES IS 1 EF, M-1 SHOWS 3. | | | SEPERATE THE EQUIPTMENT SCHEDULES, OCCUPANCY LOADS AND | | | ENERGY CALCS FOR THE 2 BUILDINGS | | | S-4 INDICATES 3 CONDENSERS ON THE PHARMACY AND 2 | | | AIRHANDLERS INSIDE. | | | THIS MAY NOT BE A COMPLETE LIST OF ITEMS MISSING OR | | | INCORRECT. | | | CORRECT AND RESUBMIT |
|