| 2014-09-23 07:06:29 | BUILDING PLAN REVIEW |
| | PERMIT: 14080956 |
| | ADD: 4201 GEORGIA AVE |
| | CONT: JOHN ROSSI |
| | TEL: (561)659-5505 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. SEPT. 23/2014 |
| | ACTION: DENIED |
| | |
| | DESCRIPTION OF WORK: NEW CONSTRUCTION THE BUILDING OF 2 |
| | BUILDINGS ONE A PHARMACY, THE SECOND A WAREHOUSE. |
| | |
| | 1) PLEASE SUBMIT A PERMIT APPLICATION FOR BOTH |
| | BUILDINGS FOR RECORD KEEPING PURPOSES. CALLING IN |
| | INSPECTIONS WILL BE DIFFICULT AS WELL AS WHEN TIME TO |
| | PRINT CERTIFICATES OF OCCUPANCY, WE CAN NOT PRINT TWO |
| | CERTIFICATE OF OCCUPANCIES UNDER ONE PERMIT FOR TWO |
| | DIFFERENT OCCUPANCIES.PLEASE SPLIT THE VALUE OF EACH |
| | BUILDING ACCORDINGLY AND WE WILL ASSESS THE PERMIT FEES |
| | FOR EACH BUILDING FOR PLANS REVIEW & INSPECTIONS. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2.1.4 THE BUILDING |
| | OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY, |
| | OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER |
| | TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM. |
| | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| | RECORDS MANAGEMENT. |
| | |
| | 2) 2010 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE |
| | CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL |
| | IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO |
| | THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| | OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| | GEOTECHNICAL INVESTIGATION BE CONDUCTED. 1803.6 |
| | REPORTING. WHERE GEOTECHNICAL INVESTIGATIONS ARE |
| | REQUIRED, A WRITTEN REPORT OF THE INVESTIGATIONS SHALL |
| | BE SUBMITTED TO THE BUILDING OFFICIAL BY THE OWNER OR |
| | AUTHORIZED AGENT AT THE TIME OF PERMIT APPLICATION. |
| | |
| | 3) PROVIDE ENERGY CALCULATIONS. 103.3 EXAMINATION OF |
| | DOCUMENTS. THE CODE OFFICIAL SHALL EXAMINE OR CAUSE TO |
| | BE EXAMINED THE ACCOMPANYING CONSTRUCTION DOCUMENTS AND |
| | SHALL ASCERTAIN WHETHER THE CONSTRUCTION INDICATED AND |
| | DESCRIBED IS IN ACCORDANCE WITH THE REQUIREMENTS OF |
| | THIS CODE AND OTHER PERTINENT LAWS OR ORDINANCES. |
| | |
| | 103.2.2 DETAILS REQUIRED. CONSTRUCTION DOCUMENTS SHALL |
| | BE DRAWN TO SCALE UPON SUITABLE MATERIAL. CONSTRUCTION |
| | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE |
| | THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED, |
| | AND SHOW IN SUFFICIENT DETAIL PERTINENT DATA AND |
| | FEATURES OF THE BUILDING, SYSTEMS AND EQUIPMENT AS |
| | HEREIN GOVERNED. DETAILS SHALL INCLUDE, BUT ARE NOT |
| | LIMITED TO, AS APPLICABLE, INSULATION MATERIALS AND |
| | THEIR R-VALUES; FENESTRATION U-FACTORS AND SHGCS; |
| | AREA-WEIGHTED U-FACTOR AND SHGC CALCULATIONS; |
| | MECHANICAL SYSTEM DESIGN CRITERIA; MECHANICAL AND |
| | SERVICE WATER HEATING SYSTEM AND EQUIPMENT TYPES, SIZES |
| | AND EFFICIENCIES; ECONOMIZER DESCRIPTION; EQUIPMENT AND |
| | SYSTEMS CONTROLS; FAN MOTOR HORSEPOWER (HP) AND |
| | CONTROLS; DUCT SEALING, DUCT AND PIPE INSULATION AND |
| | LOCATION; LIGHTING FIXTURE SCHEDULE WITH WATTAGE AND |
| | CONTROL NARRATIVE; AND AIR SEALING DETAILS. |
| | |
| | 4) PRODUCT APPROVALS NOTE IF THEY ARE FOR BOTH |
| | BUILDINGS OR IF FOR A PARTICULAR BUILDING WHICH |
| | BUILDING, SINCE THE PLANS AND PRODUCT APPROVALS ARE |
| | SUBMITTED AS ONE PACKAGE. 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 5) BOTH BUILDINGS THE PRESSURES ARE IN VULT, PLEASE |
| | ALSO SHOW VASD SINCE THE PRODUCT APPROVALS ARE TESTED |
| | IN VASD. 2010 FBC-B 1609.3.1 WIND SPEED CONVERSION. |
| | WHEN REQUIRED, ULTIMATE DESIGN WIND SPEEDS OF FIGURE |
| | 1609A, B AND C SHALL BE CONVERTED TO NOMINAL DESIGN |
| | WIND SPEEDS, VASD, USING TABLE 1609.3.1 OR EQUATION |
| | 16-32. PRODUCT APPROVALS NOT REVIEWED, PRESSURES NOT IN |
| | VASD. |
| | |
| | 6) MISSING: 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31) (D) ROOFING PRODUCTS AND ASSEMBLIES ONLY PAGE |
| | 13-0129.16 WAS SUBMITTED/ NOTE WILL REQUIRE ENHANCED |
| | FASTENING, LIMITATION #7. |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 7) PLEASE PROVIDE WIND DESIGN FOR A/C CONDENSOR |
| | SCREENING AND FRAME, AND ATTACHMENT TO STRUCTURE, |
| | MWFRS. 2010 EITHER 3105.4.2.1 OR 3105.4.2.2. |
| | |
| | 8) SHEET A-3. PLEASE PROVIDE COMPLIANCE WITH THE 2010 |
| | FBC-B 1509.6 EQUIPMENT AND APPLIANCES ON ROOFS OR |
| | ELEVATED STRUCTURES. |
| | WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE |
| | INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT |
| | EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE |
| | PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE |
| | EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO |
| | THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH |
| | ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS |
| | GREATER THAN 30 INCHES (762 MM) HIGH OR WALKING ON |
| | ROOFS HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN |
| | 12 UNITS HORIZONTAL (33-PERCENT SLOPE). |
| | PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED |
| | ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN |
| | CRITERIA: |
| | 1. THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR |
| | ROOF EDGE NOT LESS THAN 30 INCHES (762 MM). |
| | 2. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14 |
| | INCHES (356 MM) ON CENTER. |
| | 3. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN 6 |
| | INCHES (152 MM) DEEP. |
| | 4. THERE SHALL BE A MINIMUM OF 18 INCHES (457 MM) |
| | BETWEEN RAILS. |
| | 5. RUNGS SHALL HAVE A MINIMUM 0.75-INCH (19 MM) |
| | DIAMETER AND BE CAPABLE OF WITHSTANDING A 300-POUND |
| | (136.1 KG) LOAD. |
| | 6. LADDERS OVER 30 FEET (9144 MM) IN HEIGHT SHALL BE |
| | PROVIDED WITH OFFSET SECTIONS AND LANDINGS CAPABLE OF |
| | WITHSTANDING 100 POUNDS |
| | PER SQUARE FOOT. |
| | 7. LADDERS SHALL BE PROTECTED AGAINST CORROSION BY |
| | APPROVED MEANS. CATWALKS INSTALLED TO PROVIDE THE |
| | REQUIRED ACCESS SHALL BE NOT L |
| | LESS THAN 24 INCHES (610 MM) WIDE AND SHALL HAVE |
| | RAILINGS AS REQUIRED FOR SERVICE PLATFORMS. |
| | |
| | NEW PHARMACY BUILDING: |
| | |
| | 9) LIFE SAFETY SHEET LS-1 PLEASE REVIEW THE 2010 FBC-B |
| | TABLE 1004.1.1 FOR 1ST FLOOR MERCANTILE OCCUPANT LOAD |
| | IS 30 SQ FT / OCCUPANT GROSS. |
| | |
| | 10) SHEET A3 PLEASE PROVIDE MANUFACTURERS SPEC FOR |
| | ALUMINUM SUN SCREENS, AND THE INSTALATION AND ANCHORING |
| | TO STRUCTURE. 2010 FBC-B 1609. / 3105.5.1 LOADS. RIGID |
| | AWNINGS AND CANOPY SHUTTERS SHALL BE DESIGNED TO RESIST |
| | THE LOADS SET FORTH IN CHAPTER 16 OF THIS CODE EXCEPT |
| | THAT STRUCTURES OR PARTS THEREOF WHICH ARE INTENDED TO |
| | BE REMOVED OR REPOSITIONED DURING PERIODS OF HIGH WIND |
| | VELOCITY SHALL BE DESIGNED IN THEIR OPEN OR EXTENDED |
| | POSITION TO DESIGN PRESSURES BASED ON A BASIC WIND |
| | SPEED OF MINIMUM 115 MPH, 3-SECOND WIND GUST WITH |
| | APPLICABLE SHAPE FACTORS AND TO RESIST NOT LESS THAN 10 |
| | PSF (478 PA) ROOF LIVE LOAD. |
| | |
| | 11) NEITHER SHEET A3 NOR A5 SHOW THE ACTUAL HEIGHT AND |
| | LOCATION IN RELATION TO THE FINISH ROOF LEVEL 2010 |
| | FBC-B 1503.4.2. |
| | |
| | 12) PLEASE ALSO SHOW COMPLIANCE WITH 1503.4.2.1 |
| | OVERFLOW SCUPPERS BEING BETWEEN 2 TO 4 INCHES ABOVE THE |
| | FINISH ROOF LINE. |
| | |
| | 13) SHEET A5 DOES NOT SHOW THE EXTERIOR WALL INSULATION |
| | ABOVE THE CEILING, PLEASE SHOW COMPLIANCE WITH 2010 |
| | FBC-ENERGY 502.3.5.2 UNVENTED DROPPED CEILING CAVITIES. |
| | WHERE UNVENTED DROPPED CEILING CAVITIES OCCUR OVER |
| | CONDITIONED SPACES THAT DO NOT HAVE AN AIR BARRIER |
| | BETWEEN THE CONDITIONED AND UNCONDITIONED SPACE (SUCH |
| | AS T-BAR CEILINGS), THEY SHALL BE COMPLETELY SEALED |
| | FROM THE EXTERIOR ENVIRONMENT (AT THE ROOF PLANE) AND |
| | ADJACENT SPACES BY A CONTINUOUS AIR BARRIER THAT IS |
| | ALSO SEALED TO THE AIR BARRIER OF THE WALLS. IN THAT |
| | CASE, THE ROOF ASSEMBLY SHALL CONSTITUTE BOTH THE UPPER |
| | THERMAL ENVELOPE AND PRESSURE ENVELOPE OF THE BUILDING. |
| | |
| | 14) SHEET AS ALSO SHOWS ICYENE SPRAY INSULATION OF THE |
| | BOTTOM OF THE ROOF DECK. PLEASE PROVIDE THE |
| | MANUFACTURERS TEST REPORT AND COMPLIANCE WITH: 2010 |
| | FBC-B 2603.4.1.6 ATTICS AND CRAWL SPACES. |
| | WITHIN AN ATTIC OR CRAWL SPACE WHERE ENTRY IS MADE ONLY |
| | FOR SERVICE OF UTILITIES, FOAM PLASTIC INSULATION SHALL |
| | BE PROTECTED AGAINST IGNITION BY 11/2-INCH-THICK (38 |
| | MM) MINERAL FIBER INSULATION; 1/4-INCH-THICK (6.4 MM) |
| | WOOD STRUCTURAL PANEL, PARTICLEBOARD OR HARDBOARD; |
| | 3/8-INCH (9.5 MM) GYPSUM WALLBOARD, CORROSION-RESISTANT |
| | STEEL HAVING A BASE METAL THICKNESS OF 0.016 INCH (0.4 |
| | MM) OR OTHER APPROVED MATERIAL INSTALLED IN SUCH A |
| | MANNER THAT THE FOAM PLASTIC INSULATION IS NOT EXPOSED. |
| | THE PROTECTIVE COVERING SHALL BE CONSISTENT WITH THE |
| | REQUIREMENTS FOR THE TYPE OF CONSTRUCTION. |
| | |
| | WAREHOUSE |
| | |
| | 15) SHEET A3 SHOWS THE OFFICE WALLS TO BE INSULATED, A |
| | CUT SECTION LABELED A-A/A-6 SHOWS THESE WALLS NOT GOING |
| | FULL HEIGHT, NO INSULATION IS SHOWN IN THE FRAME WALLS, |
| | NOR THE CEILING JOIST CEILING OR EXTERIOR WALL. THIS |
| | DETAIL LACKS THE TYPE OF FRAMING, IF THE CEILING JOIST |
| | ARE GOING TO HAVE LIVE LOADS ABOVE THE OFFICE SPACE |
| | (MEZZANINE LEVEL). IF SO WHAT WILL THE DESIGN CRITERIA |
| | BE 125 LIGHT OR 250 HEAVY 2010 FBC-B 1607.1. |
| | 107.2.1.3 ADDITIONAL DATA. THE BUILDING OFFICIAL MAY |
| | REQUIRE DETAILS, COMPUTATIONS, STRESS DIAGRAMS, AND |
| | OTHER DATA NECESSARY TO DESCRIBE THE CONSTRUCTION OR |
| | INSTALLATION AND THE BASIS OF CALCULATIONS. |
| | |
| | 16) PLEASE TAKE NOTE THE PLANS DO NOT INDICATE WHERE |
| | THE INSULATION WILL BE LOCATED IN REGUARDS TO THE |
| | CEILING JOIST. 2010 FBC-B ENERGY 502.2.1.2 CEILING |
| | INSULATION. |
| | |
| | SHEET A4 PLEASE PROVIDE MANUFACTURERS SPEC FOR ALUMINUM |
| | SUN SCREENS, AND THE INSTALATION AND ANCHORING TO |
| | STRUCTURE. 2010 FBC-B 1609. / 3105.5.1 LOADS. RIGID |
| | AWNINGS AND CANOPY SHUTTERS SHALL BE DESIGNED TO RESIST |
| | THE LOADS SET FORTH IN CHAPTER 16 OF THIS CODE EXCEPT |
| | THAT STRUCTURES OR PARTS THEREOF WHICH ARE INTENDED TO |
| | BE REMOVED OR REPOSITIONED DURING PERIODS OF HIGH WIND |
| | VELOCITY SHALL BE DESIGNED IN THEIR OPEN OR EXTENDED |
| | POSITION TO DESIGN PRESSURES BASED ON A BASIC WIND |
| | SPEED OF MINIMUM 115 MPH, 3-SECOND WIND GUST WITH |
| | APPLICABLE SHAPE FACTORS AND TO RESIST NOT LESS THAN 10 |
| | PSF (478 PA) ROOF LIVE LOAD. |
| | |
| | 17) SHEET A-6 SHOWS ICYENE SPRAY INSULATION OF THE |
| | BOTTOM OF THE ROOF DECK. PLEASE PROVIDE THE |
| | MANUFACTURERS TEST REPORT AND COMPLIANCE WITH: 2010 |
| | FBC-B 2603.4.1.6 ATTICS AND CRAWL SPACES. |
| | WITHIN AN ATTIC OR CRAWL SPACE WHERE ENTRY IS MADE ONLY |
| | FOR SERVICE OF UTILITIES, FOAM PLASTIC INSULATION SHALL |
| | BE PROTECTED AGAINST IGNITION BY 11/2-INCH-THICK (38 |
| | MM) MINERAL FIBER INSULATION; 1/4-INCH-THICK (6.4 MM) |
| | WOOD STRUCTURAL PANEL, PARTICLEBOARD OR HARDBOARD; |
| | 3/8-INCH (9.5 MM) GYPSUM WALLBOARD, CORROSION-RESISTANT |
| | STEEL HAVING A BASE METAL THICKNESS OF 0.016 INCH (0.4 |
| | MM) OR OTHER APPROVED MATERIAL INSTALLED IN SUCH A |
| | MANNER THAT THE FOAM PLASTIC INSULATION IS NOT EXPOSED. |
| | THE PROTECTIVE COVERING SHALL BE CONSISTENT WITH THE |
| | REQUIREMENTS FOR THE TYPE OF CONSTRUCTION. |
| | INSULATION INSTALLED ON A SUSPENDED CEILING WITH |
| | REMOVABLE CEILING TILES SHALL NOT BE CONSIDERED PART OF |
| | THE MINIMUM THERMAL RESISTANCE OF THE ROOF INSULATION |
| | UNLESS THE ROOF/CEILING CAVITY IS SEALED FROM THE |
| | EXTERIOR ENVIRONMENT. |
| | |
| | 18) SHEET A-3. PLEASE PROVIDE COMPLIANCE WITH THE 2010 |
| | FBC-B 1509.6 EQUIPMENT AND APPLIANCES ON ROOFS OR |
| | ELEVATED STRUCTURES. |
| | WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE |
| | INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT |
| | EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE |
| | PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE |
| | EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO |
| | THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH |
| | ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS |
| | GREATER THAN 30 INCHES (762 MM) HIGH OR WALKING ON |
| | ROOFS HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN |
| | 12 UNITS HORIZONTAL (33-PERCENT SLOPE). |
| | PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED |
| | ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN |
| | CRITERIA: |
| | 1. THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR |
| | ROOF EDGE NOT LESS THAN 30 INCHES (762 MM). |
| | 2. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14 |
| | INCHES (356 MM) ON CENTER. |
| | 3. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN 6 |
| | INCHES (152 MM) DEEP. |
| | 4. THERE SHALL BE A MINIMUM OF 18 INCHES (457 MM) |
| | BETWEEN RAILS. |
| | 5. RUNGS SHALL HAVE A MINIMUM 0.75-INCH (19 MM) |
| | DIAMETER AND BE CAPABLE OF WITHSTANDING A 300-POUND |
| | (136.1 KG) LOAD. |
| | 6. LADDERS OVER 30 FEET (9144 MM) IN HEIGHT SHALL BE |
| | PROVIDED WITH OFFSET SECTIONS AND LANDINGS CAPABLE OF |
| | WITHSTANDING 100 POUNDS |
| | PER SQUARE FOOT. |
| | 7. LADDERS SHALL BE PROTECTED AGAINST CORROSION BY |
| | APPROVED MEANS. CATWALKS INSTALLED TO PROVIDE THE |
| | REQUIRED ACCESS SHALL BE NOT L |
| | LESS THAN 24 INCHES (610 MM) WIDE AND SHALL HAVE |
| | RAILINGS AS REQUIRED FOR SERVICE PLATFORMS. |
| | |
| | 19) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |