2014-09-19 10:43:00DATE: 9/18/2014
 PROJECT: FAU SCOREBOARDS
 PERMIT#: 14080953
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 SITE AND ELECTRICAL PLANS FOR SCOREBOARDS ON PERMIT
 #12110275.
  
 1) 600.3 LISTING.
 ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING ?
 FIXED, MOBILE, OR PORTABLE ? SHALL BE LISTED AND
 INSTALLED IN CONFORMANCE WITH THAT LISTING, UNLESS
 OTHERWISE APPROVED BY SPECIAL PERMISSION.
  
 2) 600.4 MARKINGS.
 (A) SIGNS AND OUTLINE LIGHTING SYSTEMS. SIGNS AND
 OUTLINE LIGHTING SYSTEMS SHALL BE MARKED WITH THE
 MANUFACTURER?S NAME, TRADEMARK, OR OTHER MEANS OF
 IDENTIFICATION; AND INPUT VOLTAGE AND CURRENT RATING.
 (B) SIGNS WITH LAMPHOLDERS FOR INCANDESCENT LAMPS.
 SIGNS AND OUTLINE LIGHTING SYSTEMS WITH LAMPHOLDERS FOR
 INCANDESCENT LAMPS SHALL BE MARKED TO INDICATE THE
 MAXIMUM ALLOWABLE LAMP WATTAGE PER LAMPHOLDER. THE
 MARKINGS SHALL BE PERMANENTLY INSTALLED, IN LETTERS AT
 LEAST 6 MM (1?4 IN.) HIGH, AND SHALL BE LOCATED WHERE
 VISIBLE DURING RELAMPING.
 (C) SECTION SIGNS. SECTION SIGNS SHALL BE MARKED TO
 INDICATE THAT FIELD-WIRING AND INSTALLATION
 INSTRUCTIONS ARE REQUIRED. THE ELECTRICAL CONNECTIONS
 TO SAME ARE UNDER A DIFFERENT PERMIT.
  
 3) NEC 600.6(A)(1) LOCATION.
 DISCONNECTS. EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR
 FEEDER CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR
 OUT-LINE LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN
 EXTERNALLY OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL
 OPEN ALL UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN
 OR OUTLINE LIGHTING SYSTEM THAT IT CONTROLS.
  
 4) FBC-E 505.2 ENERGY CONSERVATION
 ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL
 HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN
 NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME
 CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES
 SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS
 OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E 505.2
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]