| Plan Review Notes For Permit 14080942 |
| Permit Number |
14080942 |
|
| Review Stop |
G |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2015-02-15 05:58:37 | 1) SUBMIT COPIES OF THE APPLICABLE GAS SIZING TABLE | | | FROM THE 2010 FBCR SEC. G2413.3 OR REFERENCE THE | | | SPECIFIC SIZING TABLES ON THE PLANS FOR EACH TYPE OF | | | PIPE MATERIAL USED FOR THE GAS SYSTEM. 3RD REQUEST. | | | 2) SUBMIT MANUFACTURER SPECIFICATION SHEETS FOR THE GAS | | | REGULATORS. REGULATORS SHALL COMPLY W/ 2010 FBCR | | | SEC.G2421.3. 3RD REQUEST. | | | 3) SPECS FOR A GAS RANGE HAVE BEEN SUBMITTED AND A GAS | | | RANGE IS SHOWN ON THE GAS RISER.THE ZONING CODE DOES | | | NOT ALLOW A KITCHEN IN THIS STRUCTURE AS IT CAN ONLY BE | | | USED AS AN ACCESSORY STRUCTURE TO THE MAIN HOUSE. | | | REMOVE THE THE GAS RANGE PIPNG FROM THE GAS RISER | | | DIAGRAM COMPLETELY. DO NOT SHOW A CAPPED LINE. | | | 4) SUBMIT 2 COPIES OF A FULL SET OF MANUFACTURER'S | | | SPECIFICATIONS FOR THE PORTABLE GENERATOR AND THE GAS | | | BBQ GRILL. THE INFORMATION THAT WAS SUBMITTED IS | | | INADEQUATE AND INCOMPLETE. WPB AMEND. TO 2010 FBC SEC. | | | 107.2.1.3RD REQUEST. | | | | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|