| 2014-12-22 14:40:38 | 1) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE |
| | GENERATOR & BBQ GRILL. FBCR SEC.G2404.3. 2ND REQUEST |
| | 2) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE |
| | TANKLESS WATER HEATER PER SEC.304 OF THE 2010 FBCR |
| | SEC.G2407 |
| | 3) SUBMIT COPIES OF THE APPLICABLE GAS SIZING TABLE |
| | FROM THE 2010 FBCR SEC. G2413.3. |
| | 4) SHOW THE TOTAL DISTANCE FROM THE GAS POINT OF |
| | DELIVERY TO THE MOST REMOTE OUTLET. FBCR SEC. G2413.3. |
| | 5) SHOW THE PIPE SIZES FOR ALL SECTIONS OF THE PIPING |
| | SYSTEM.WPB AMEND. TO 2010 FBC SEC.107.2.1. |
| | 6) THE VENT SHALL TERMINATE A MINIMUM OF 2 FT. ABOVE |
| | THE WALL/ROOF PER 2010 FBCR SEC.G2427.6.3 OR MANUF. |
| | INSTALLATION INSTRUCTIONS. SHOW THIS ON THE PLAN. 2ND |
| | REQUEST. |
| | 7) GALVANIZED PIPING IS NOT APPROVED FOR USE |
| | UNDERGROUND PER THE 2010 FBCR SEC.G2414.8, G2415.9. |
| | 8) THE PRESSURE REGULATOR FOR THE TANKLESS WATER HEATER |
| | SHALL BE VENTED TO THE EXTERIOR PER THE 2010 FBCR |
| | SEC.2421.3. |
| | 9) SUBMIT MANUF. SPEC. SHEETS FOR THE |
| | REGULATORS.REGULATORS SHALLL COMPLY WITH 2010 FBCR |
| | SEC.G2421.1. |
| | 10) A LISTED SHUTOFF VALVE SHALL BE LOCATED IMMEDIATELY |
| | AHEAD OF EACH MP (MEDIUM PRESSURE) REGULATOR.FBCR |
| | SEC.G2420.4. |
| | SEARCH OF CITY RECORDS SHOWS A PERMIT WAS ONLY ISSUED |
| | FOR THE RANGE. ANY OTHER GAS WORK THAT HAS BEEN |
| | INSTALLED HAS BEEN DONE WITHOUT THE PROPER PERMITS OR |
| | INSPECTIONS AND SHALL BE EXPOSED FOR INSPECTION. |
| | |
| | |