Plan Review Notes
Plan Review Notes For Permit 14080942
Permit Number 14080942
Review Stop G
Sequence Number 2
Notes
Date Text
2014-12-22 14:40:381) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE
 GENERATOR & BBQ GRILL. FBCR SEC.G2404.3. 2ND REQUEST
 2) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 TANKLESS WATER HEATER PER SEC.304 OF THE 2010 FBCR
 SEC.G2407
 3) SUBMIT COPIES OF THE APPLICABLE GAS SIZING TABLE
 FROM THE 2010 FBCR SEC. G2413.3.
 4) SHOW THE TOTAL DISTANCE FROM THE GAS POINT OF
 DELIVERY TO THE MOST REMOTE OUTLET. FBCR SEC. G2413.3.
 5) SHOW THE PIPE SIZES FOR ALL SECTIONS OF THE PIPING
 SYSTEM.WPB AMEND. TO 2010 FBC SEC.107.2.1.
 6) THE VENT SHALL TERMINATE A MINIMUM OF 2 FT. ABOVE
 THE WALL/ROOF PER 2010 FBCR SEC.G2427.6.3 OR MANUF.
 INSTALLATION INSTRUCTIONS. SHOW THIS ON THE PLAN. 2ND
 REQUEST.
 7) GALVANIZED PIPING IS NOT APPROVED FOR USE
 UNDERGROUND PER THE 2010 FBCR SEC.G2414.8, G2415.9.
 8) THE PRESSURE REGULATOR FOR THE TANKLESS WATER HEATER
 SHALL BE VENTED TO THE EXTERIOR PER THE 2010 FBCR
 SEC.2421.3.
 9) SUBMIT MANUF. SPEC. SHEETS FOR THE
 REGULATORS.REGULATORS SHALLL COMPLY WITH 2010 FBCR
 SEC.G2421.1.
 10) A LISTED SHUTOFF VALVE SHALL BE LOCATED IMMEDIATELY
 AHEAD OF EACH MP (MEDIUM PRESSURE) REGULATOR.FBCR
 SEC.G2420.4.
 SEARCH OF CITY RECORDS SHOWS A PERMIT WAS ONLY ISSUED
 FOR THE RANGE. ANY OTHER GAS WORK THAT HAS BEEN
 INSTALLED HAS BEEN DONE WITHOUT THE PROPER PERMITS OR
 INSPECTIONS AND SHALL BE EXPOSED FOR INSPECTION.
  
  