Plan Review Notes
Plan Review Notes For Permit 14080942
Permit Number 14080942
Review Stop E
Sequence Number 2
Notes
Date Text
2015-01-08 11:03:18DATE: 01/08/2015
 PROJECT: PARADELO
 PERMIT#: 14080942
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 AS CLEARLY INDICATED IN THE PREVIOUS REVIEWS, THE CITY
 RECORDS INDICATE THAT THE STRUCTURE SHOWN ON THE
 DRAWINGS IS A DETACHED GARAGE. NO RECORDS COULD BE
 LOCATED TO INDICATE THE BATHROOM, KITCHEN, OR TANKLESS
 GAS WATER HEATER WERE ADDED TO THE GARAGE WITH THE
 REQUIRED PERMITS AND INSPECTIONS. SEE BUILDING,
 PLUMBING AND ZONING COMMENTS. ASIDE FROM THE BUILDING
 AND ZONING COMMENTS, THERE ARE SERVERE DESIGN FLAWS
 THROUGHOUT THE ELECTRICAL PLAN SUBMITTED. COSIDER
 CONSULTING WITH A DESIGN PROFESSIONAL FOR SOME
 ASSISTANCE IN COMPLETING THIS OVERALL DESIGN.
 PROVIDED IT IS ALLOWED BY BUILDING, PLUMBING AND ZONING
 AND IN ORDER TO MAKE THE CONVERSION MEET CURRENT
 ELECTRICAL CODE THE FOLLOWING COMMENTS WOULD NEED TO BE
 ADDRESSED:
  
 1) SUFFICIENT CLEAR ACCESS AND DEDICATED WORKING SPACE
 SHALL BE PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL
 EQUIPMENT TO ALLOW READY AND SAFE OPERATION AND
 MAINTENANCE OF SUCH EQUIPMENT. NEC 110.26 THE KITCHEN
 COUNTER TOP, REFRIGERATOR, DRYER, AND TANKLESS WATER
 HEATER APPEAR TO BE ENCROACHING ON THE REQUIRED WORKING
 CLEARANCES DESCRIBED IN THE NEC 110.26.
  
 2) THE SERVICE DISCONNECTING MEANS SHALL BE INSTALLED
 AT A READILY ACCESSIBLE LOCATION EITHER OUTSIDE OF A
 BUILDING OR STRUCTURE OR INSIDE NEAREST THE POINT OF
 ENTRANCE OF THE SERVICE CONDUCTORS. NEC 230.70(A)(1)
 INDICATE THE LOCATION OF THE ELECTRICAL SERVICE AND THE
 FEED TO THE PANEL IN THE GARAGE.THE SUB PANEL AT THE
 UTILITY STRUCTURE IS INDICATED TO BE FED FROM THE HOUSE
 PANEL WITH A 50AMP BREAKER ON #1 WIRE WITH A 175AMP
 TOTAL CONNECTED LOAD INDICATED AT THE SUB PANEL WITH A
 100AMP MAIN BREAKER.
  
 3) PROVIDE A REVISED RISER DIAGRAM, LOAD CALCULATION
 AND PANEL DIRECTORIES SHOWING COMPLETE FEEDER DETAILS
 AREA IN SQUARE FEET OF THE BUILDING, THE TOTAL
 CALCULATED LOAD BEFORE APPLYING DEMAND FACTORS, THE
 DEMAND FACTORS USED, THE CALCULATED LOAD AFTER APPLYING
 DEMAND FACTORS, AND THE SIZE AND TYPE OF CONDUCTORS TO
 BE USED. NEC 215.5 THE RISER DIAGRAM SUBMITTED DOES NOT
 ADAQUATELY MEET THE MINIMUM DESIGN CRITERIA REQUIRED.
 PROVIDE THE GROUNDING ELECTRODE DETAIL, THE UTILITY
 METERING, SUBMITTALS ON THE GENERATOR AND MTS, A
 REVISED DESIGN IS REQUIRED ON THE RISER TO INDICATE HOW
 THE MTS AND GENERATOR WILL PROVIDE OPTIONAL STANDBY
 POWER FOR THE SERVICE WITHOUT A BACKFEED. THE LOADS
 CALCULATED ON THE PLAN INDICATE A TOTAL OF 415 AMPS
 WITH A 200 AMP MAIN AND A 2/0 FEEDER. THE SUB PANEL AT
 THE UTILITY STRUCTURE IS INDICATED TO BE FED FROM THE
 HOUSE PANEL WITH A 50AMP BREAKER ON #1 WIRE WITH A
 175AMP TOTAL CONNECTED LOAD INDICATED AT THE SUB PANEL.
  
 4) EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE
 LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND
 SPECIFIC PURPOSE OR USE. NEC 408.4 PROVIDE REVISED
 PANEL SCHEDULES.THE PANEL SCHEDULES DO NOT ADAQUATELY
 INDICATE ALL REQUIRED CIRCUITRY OR SHOW ALL CIRCUITRY
 USED ON THE PLAN. THE PANEL SCHEDULE MUST COINCIDE WITH
 THE CIRCUITRY ON THE FLOOR PLAN. NOT ALL CIRCUITS ON
 THE FLOOR PLAN ARE INDICATED IN THE PANEL SCHEDULE.
  
 5) ALL GROUNDING ELECTRODES AS DESCRIBED IN
 250.52(A)(1) THROUGH (A)(7) THAT ARE PRESENT AT EACH
 BUILDING OR STRUCTURE SERVED SHALL BE BONDED TOGETHER
 TO FORM THE GROUNDING ELECTRODE SYSTEM. NEC 250.50
  
 6) WHERE INSTALLED IN OR ATTACHED TO A BUILDING OR
 STRUCTURE, A METAL PIPING SYSTEM(S), INCLUDING GAS
 PIPING, THAT IS LIKELY TO BECOME ENERGIZED SHALL BE
 BONDED TO THE SERVICE EQUIPMENT ENCLOSURE, THE GROUNDED
 CONDUCTOR AT THE SERVICE, THE GROUNDING ELECTRODE
 CONDUCTOR WHERE OF SUFFICIENT SIZE, OR THE ONE OR MORE
 GROUNDING ELECTRODES USED NEC 250.104(3)(B)
  
 7) THE CONNECTION OF A GROUNDING ELECTRODE CONDUCTOR AT
 EACH BUILDING OR STRUCTURE WHERE SUPPLIED BY A
 FEEDER(S) OR BRANCH CIRCUIT(S), SHALL BE MADE AS
 SPECIFIED 250.32, 250.68(A) AND (B).
  
 8) THE VALUE OF THE PROJECT ISN?T REALISTIC AND WILL BE
 REVISED TO INCLUDE THE OVERALL SCOPE OF WORK. FBC WPB
 AMENDMENTS. SECTION 109.3
  
 9) THE PLAN IS STILL NOT SIGNED BY THE DESIGNER. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS TO FBC
 107.2.1
  
 10) A SEPARATE ELECTRICAL PERMIT APPLICATION IS STILL
 REQUIRED WITH THE SUBMITTAL FOR THE ISSUANCE OF AN
 ELCTRICAL PERMIT FOR THE INSTALLATION OF PROPOSED
 ELECTRICAL SCOPE.
  
 11) A SEPARATE ELECTRICAL PERMIT APPLICATION
 ACCOMPANIED BY THE MANUFACTURER PRODUCT APPROVAL
 DOCUMENTATION IS REQUIRED FOR THE GENERATOR AND MTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  