| Plan Review Notes For Permit 14080942 |
| Permit Number |
14080942 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-01-08 10:57:17 | 2ND REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | BUILDING | | | | | | THE PLANS THAT WERE RESUBMITTED INDICATE THAT THE | | | STRUCTURE WILL BE USED AS A STORAGE/UTILITY ROOM. THIS | | | IS NOT CONSIDERED A CHANGE OF OCCUPANCY FROM A GARAGE. | | | THEREFORE, ONLY THE IMPROVEMENTS THAT WERE DONE WITHOUT | | | PERMITS AND INSPECTIONS WILL NEED TO BE ADDRESSED. I | | | COULD NOT LOCATE ANY RECORDS THAT INDICATE THAT THE | | | WORK TO ADD THE BATHROOM, UTILITY SINK OR TANKLESS GAS | | | WATER HEATER TO THE GARAGE WAS DONE WITH THE REQUIRED | | | PERMITS AND INSPECTIONS. UNLESS YOU CAN PROVIDE | | | DOCUMENTATION THAT THE WORK WAS PERMITTED AND | | | INSPECTED, THE WORK WILL BE REQUIRED TO COMPLY WITH THE | | | 2010 FBC AND 2008 NEC. ALL OF THE WORK IS REQUIRED TO | | | BE PERMITTED AND INSPECTED. YOU CAN CONTACT DIANNE | | | FULCHER VIA EMAIL AT [email protected] IF YOU WISH TO | | | MAKE A RESEARCH REQUEST. SEE ZONING COMMENTS. | | | | | | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|