2014-09-16 06:37:131) CITY RECORDS DO NOT SHOW ANY PERMITS THAT WERE
 ISSUED FOR THE INSTALLATION OF THE PLUMBING WORK THAT
 IS PRESENT. THIS WORK SHALL BE LEGALLY PERMITTTED AND
 INSPECTED OR IT SHALL BE REMOVED IF NOT PERMITTED BY
 THE ZONING DEPT. SEE ZONING COMMENTS.WPB ADMIN. AMEND.
 TO 2010 FBC SEC.105.1.
 2) SHOW THE SHOWER DIMENSIONS ( LXW) ON THE PLANS. THE
 SHOWER SHALL BE A MIN. OF 30" IN WIDTH AND A MIN. OF
 900 SQ. INCHES. 2010 FBCR SEC.P2708.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR