Plan Review Notes
Plan Review Notes For Permit 14080942
Permit Number 14080942
Review Stop G
Sequence Number 1
Notes
Date Text
2014-09-15 14:19:581) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE
 TANKLESS WATER HEATER, GENERATOR,& BBQ GRIL. FBCR
 SEC.G2404.3.
 2) SUBMIT A LEGIBLE GAS DRAWING. THE SUBMITTED DRAWING
 IS TOO DIFFICULT TO READ DUE TO THE SMALL PRINTING.
 PLANS SHALL BE DRAWN TO A MIN. 1/8 " SCALE. WPB ADMIN.
 AMEND. TO 2010 FBC SEC.107.2.1.4.
 3) THE GAS RISER SHALL SHOW THE BTU LOAD FOR EACH
 APPLIANCE. THE BTU LOAD FOR THE TANKLESS WATER HEATER
 SHALL BE SPECIFIC ( THE PLAN SHOWS A RANGE OF
 10,300-180,000 BTU'S.
 4) SUBMIT COPIES OF THE APPLICABLE GAS SIZING TABLE FOR
 THIS INSTALLATION.
 5) SHOW THE DIMENSION OF EACH SECTION OF PIPE AND THE
 TOATAL DISTANCE FROM THE GAS POINT OF DELIVERY TO THE
 MOST REMOTE OUTLET.
 6) SHOW THE PIPE SIZES FOR ALL SECTIONS OF THE PIPING
 SYSTEM.
 7) SHOW THE TYPE OF VENT FOR THE TANKLESS WATER HEATER.
 THE VENT SHALL TERMINATE A MINIMUM OF 2 FT. ABOVE THE
 WALL/ROOF PER 2010 FBCR SEC.G2427.5.3.
 8) SEARCH OF CITY RECORDS SHOWS A PERMIT WAS ONLY
 ISSUED FOR THE RANGE. ANY OTHER GAS WORK THAT HAS BEEN
 INSTALLED HAS BEEN DONE WITHOUT THE PROPER PERMITS OR
 INSPECTIONS.
  