Date Text
2014-09-17 08:21:46DATE: 9/17/2014
 PROJECT:
 PERMIT#:
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 AS CLEARLY INDICATED IN THE PREVIOUS REVIEWS, THE CITY
 RECORDS INDICATE THAT THE STRUCTURE SHOWN ON THE
 DRAWINGS IS A DETACHED GARAGE. NO RECORDS COULD BE
 LOCATED TO INDICATE THE BATHROOM, KITCHEN, OR TANKLESS
 GAS WATER HEATER WERE ADDED TO THE GARAGE WITH THE
 REQUIRED PERMITS AND INSPECTIONS. SEE BUILDING,
 PLUMBING AND ZONING COMMENTS.
 PROVIDED IT IS ALLOWED BY BUILDING, PLUMBING AND ZONING
 AND IN ORDER TO MAKE THE CONVERSION MEET CURRENT
 ELECTRUCAL CODE THE FOLLOWING COMMENTS WOULD NEED TO BE
 ADDRESSED:
  
 1) SUFFICIENT CLEAR ACCESS AND DEDICATED WORKING SPACE
 SHALL BE PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL
 EQUIPMENT TO ALLOW READY AND SAFE OPERATION AND
 MAINTENANCE OF SUCH EQUIPMENT. NEC 110.26 THE KITCHEN
 COUTER TOP, REFRIDGERATOR, DRYER, AND TANKLESS WATER
 HEATER APPEAR TO BE ENCHROCHING ON THE REQUIRED WORKING
 CLEARANCES DESCRIBED IN THE NEC 110.26.
  
 2) BRANCH CIRCUITS FOR LIGHTING AND FOR APPLIANCES,
 INCLUDING MOTOR-OPERATED APPLIANCES, SHALL BE PROVIDED
 TO SUPPLY THE LOADS CALCULATED IN ACCORDANCE WITH
 220.10. IN ADDITION, BRANCH CIRCUITS SHALL BE PROVIDED
 FOR SPECIFIC LOADS NOT COVERED BY 220.10 WHERE REQUIRED
 ELSEWHERE IN THIS CODE AND FOR DWELLING UNIT LOADS AS
 SPECIFIED IN THE NEC 210.11(C).
 (A) NUMBER OF BRANCH CIRCUITS. THE MINIMUM NUMBER OF
 BRANCH CIRCUITS SHALL BE DETERMINED FROM THE TOTAL
 CALCULATED LOAD AND THE SIZE OR RATING OF THE CIRCUITS
 USED. IN ALL INSTALLATIONS, THE NUMBER OF CIRCUITS
 SHALL BE SUFFICIENT TO SUPPLY THE LOAD SERVED. IN NO
 CASE SHALL THE LOAD ON ANY CIRCUIT EXCEED THE MAXIMUM
 SPECIFIED BY 220.18.
 (B) LOAD EVENLY PROPORTIONED AMONG BRANCH CIRCUITS.
 WHERE THE LOAD IS CALCULATED ON THE BASIS OF
 VOLT-AMPERES PER SQUARE METER OR PER SQUARE FOOT, THE
 WIRING SYSTEM UP TO AND INCLUDING THE BRANCH-CIRCUIT
 PANELBOARD(S) SHALL BE PROVIDED TO SERVE NOT LESS THAN
 THE CALCULATED LOAD. THIS LOAD SHALL BE EVENLY
 PROPORTIONED AMONG MULTIOUTLET BRANCH CIRCUITS WITHIN
 THE PANELBOARD(S). BRANCH-CIRCUIT OVERCURRENT DEVICES
 AND CIRCUITS SHALL BE REQUIRED TO BE INSTALLED ONLY TO
 SERVE THE CONNECTED LOAD.
 (C) SMALL-APPLIANCE BRANCH CIRCUITS. IN ADDITION TO THE
 NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF
 THIS SECTION, TWO OR MORE 20-AMPERE SMALL-APPLIANCE
 BRANCH CIRCUITS SHALL BE PROVIDED FOR ALL RECEPTACLE
 OUTLETS SPECIFIED BY 210.52(B).
 (D) LAUNDRY BRANCH CIRCUITS. IN ADDITION TO THE NUMBER
 OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF THIS
 SECTION, AT LEAST ONE ADDITIONAL 20-AMPERE BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY THE LAUNDRY
 RECEPTACLE OUTLET(S) REQUIRED BY 210.52(F). THIS
 CIRCUIT SHALL HAVE NO OTHER OUTLETS.
 (E) BATHROOM BRANCH CIRCUITS. IN ADDITION TO THE NUMBER
 OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF THIS
 SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS.
  
 3) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL
 314 AND 315.
  
 4) VERIFY THE WATER HEATER HAS THE REQUIRED ELECTRIC
 DISCONNECT. NEC 422.31
  
 5) THE SERVICE DISCONNECTING MEANS SHALL BE INSTALLED
 AT A READILY ACCESSIBLE LOCATION EITHER OUTSIDE OF A
 BUILDING OR STRUCTURE OR INSIDE NEAREST THE POINT OF
 ENTRANCE OF THE SERVICE CONDUCTORS. NEC 230.70(A)(1)
 INDICATE THE LOCATION OF THE ELECTRICAL SERVICE AND THE
 FEED TO THE PANEL IN THE GARAGE.
  
 6) PROVIDE A RISER DIAGRAM SHOWING FEEDER DETAILS.
 INCLUDE THE AREA IN SQUARE FEET OF THE BUILDING, THE
 TOTAL CALCULATED LOAD BEFORE APPLYING DEMAND FACTORS,
 THE DEMAND FACTORS USED, THE CALCULATED LOAD AFTER
 APPLYING DEMAND FACTORS, AND THE SIZE AND TYPE OF
 CONDUCTORS TO BE USED. NEC 215.5
  
 7) PROVIDE A COMPLETE LOAD CALCULATION. PROVIDE A PANEL
 SCHEDULE SHOWING ALL LOADS BALANCED. INDICATE THE
 PROPOSED WIRING METHOD, WIRE SIZE WITH OVER CURRENT
 PROTECTION FOR ALL CIRCUITS. NEC 220.12, 220.14, 230.31
  
 8) ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI
 PROTECTED. NEC 210.12 NEW RECEPTACLES MUST BE TAMPER
 RESISTANT. NEC 406.11
  
 9) THE CONNECTION OF A GROUNDING ELECTRODE CONDUCTOR AT
 EACH BUILDING OR STRUCTURE WHERE SUPPLIED BY A
 FEEDER(S) OR BRANCH CIRCUIT(S), SHALL BE MADE AS
 SPECIFIED IN THE 2008 EDITION OF THE NEC ARTICLE
 250.68(A) AND (B).
  
 10) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES
 INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8)
 SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION
 FOR PERSONNEL. NEC 210.8. ALL OUTLETS IN THE KITCHEN
 SHALL BE GFCI PROTECTED.
  
 11) ARC-FAULT PROTECTION IS NOW REQUIRED IN RESIDENTIAL
 OCCUPANCIES ON ALL 15 AND 20 AMP BRANCH CIRCUITS THAT
 ARE NOT ALREADY REQUIRED TO BE PROTECTED BY GROUND
 FAULT INTERRUPTERS CIRCUITS (GFCI) OR OVER 120 VOLTS
 210.12(B)
  
 12) MULTI-WIRE BRANCH CIRCUITS THAT SHARE A COMMON
 GROUND CONDUCTOR (NEUTRAL) MUST SHARE A COMMON
 DISCONNECT OR THE NEUTRALS MUST BE DISCONNECTED AT THE
 SAME TIME 210.4(B).
  
 13) OCCUPIABLE BALCONIES AND PORCHES OVER 20 SQ FT MUST
 NOW HAVE A RECEPTACLE OUTLET (GFCI PROTECTED)
 (210.52(E)(3).
  
 14) RECEPTACLES SHALL BE INSTALLED SUCH THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL
 SPACE IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET. NEC
 210.52(A)(1)
  
 15) ANY SPACE 2 FEET OR MORE IN WIDTH (INCLUDING SPACE
 MEASURED AROUND CORNERS) AND UNBROKEN ALONG THE FLOOR
 LINE BY DOORS, FIREPLACES, AND SIMILAR OPENINGS. NEC
 210.52(A)(2)(1)
  
 16) SMALL-APPLIANCE BRANCH CIRCUITS IN ADDITION TO THE
 NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF
 THIS SECTION, TWO OR MORE 20-AMPERE SMALL-APPLIANCE
 BRANCH CIRCUITS SHALL BE PROVIDED FOR ALL RECEPTACLE
 OUTLETS SPECIFIED BY NEC 210.52(B).
  
 17) THE VALUE OF THE PROJECT ISNT REALISTIC AND WILL BE
 REVISED TO INCLUDE THE OVERALL SCOPE OF WORK. FBC WPB
 AMENDMENTS. SECTION 109.3
  
 18) FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET ACCESSIBLE WHILE STANDING AT
 GRADE LEVEL AND LOCATED NOT MORE THAN 2.0 M (61.2 FT)
 ABOVE GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF
 THE DWELLING. NEC 210.52(E)(3)
  
 19) PROVIDE MANUFACTURER PRODUCT ELECTRICAL
 SPECIFICATIONS FOR THE WALL MOUNTED A/C UNIT. INDICATE
 A COMPATABLE ELECTRICAL RECEPTACLE OUTLET FOR SAME.
  
 20) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS
 TO FBC 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,