| Plan Review Notes For Permit 14080934 |
| Permit Number |
14080934 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-08-22 14:21:59 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | ADDITIONAL HORN STROBES MAY BE NEEDED TO MEET THE | | | FOLLOWING CODE REQUIRMENT. | | | | | | PER NFPA 72 SECTION 7.4.41, SLEEPING AREA NOTIFICATION | | | APPLIANCES SHALL HAVE A SOUND LEVEL OF AT LEAST 15 DB | | | ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5 DB ABOVE THE | | | MAXIMUM SOUND LEVEL HAVING A DURATION OF AT LEAST 60 | | | SECONDS OR A SOUND LEVEL OF AT LEAST 75 DBA, WHICHEVER | | | IS GREATER, MEASURED AT THE PILLOW LEVEL IN THE AREA | | | REQUIRED TO BE SERVED BY THE SYSTEM USING THE | | | A-WEIGHTED SCALE (DBA). | | | | | | PRETEST VERIFICATION IS NEEDED ON FIRE INSPECTION. | | | | | | FIRE INSPECTOR TO FIELD VERIFY DBA. |
|