2014-09-02 09:44:45DATE: 9/2/2014
 PROJECT: IBIS TEMP TENT
 PERMIT#: 14080915
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) THERE IS NO ELECTRICAL INFORMATION INCLUDED IN
 SUBMITTAL PACKAGE. PLEASE PROVIDE THE MINIMAL PLAN
 REVIEW CRITERIA TO INCLUDE BUT NOT BE LIMITED TO THE
 FOLLOWING:
 A. A RISER DIAGRAM, LOAD CALCULATION, AND PANEL
 SCHEDULE(S)
 B. A FLOOR PLAN INDICATING GENERAL LIGHTING, LIGHTING
 CONTROL, EMERGENCY AND EXIT LIGHTING, PROVIDING A SAFE,
 ILLUMINATED MEANS OF EGRESS.
 C. THE FLOOR PLAN TO ALSO INDICATE GENERAL POWER
 OUTLET(S) GFI(S) EQUIPMENT LOCATIONS, INCLUDING LOAD
 AND VOLTAGE, WIRING METHODS, AND CONNECTION DETAILS
 INDICATING DISCONNECTS AS REQUIRED,
 D. A SITE PLAN TO INCLUDE LOCATIONS FOR UTILITIES,
 ELECTRICAL SERVICE EQUIPMENT, AIR CONDITIONING UNITS
 WITH ASSOCIATED WIRING AND DISCONNECTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  