| 2014-09-02 09:44:45 | DATE: 9/2/2014 |
| | PROJECT: IBIS TEMP TENT |
| | PERMIT#: 14080915 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) THERE IS NO ELECTRICAL INFORMATION INCLUDED IN |
| | SUBMITTAL PACKAGE. PLEASE PROVIDE THE MINIMAL PLAN |
| | REVIEW CRITERIA TO INCLUDE BUT NOT BE LIMITED TO THE |
| | FOLLOWING: |
| | A. A RISER DIAGRAM, LOAD CALCULATION, AND PANEL |
| | SCHEDULE(S) |
| | B. A FLOOR PLAN INDICATING GENERAL LIGHTING, LIGHTING |
| | CONTROL, EMERGENCY AND EXIT LIGHTING, PROVIDING A SAFE, |
| | ILLUMINATED MEANS OF EGRESS. |
| | C. THE FLOOR PLAN TO ALSO INDICATE GENERAL POWER |
| | OUTLET(S) GFI(S) EQUIPMENT LOCATIONS, INCLUDING LOAD |
| | AND VOLTAGE, WIRING METHODS, AND CONNECTION DETAILS |
| | INDICATING DISCONNECTS AS REQUIRED, |
| | D. A SITE PLAN TO INCLUDE LOCATIONS FOR UTILITIES, |
| | ELECTRICAL SERVICE EQUIPMENT, AIR CONDITIONING UNITS |
| | WITH ASSOCIATED WIRING AND DISCONNECTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT |
| | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| | ITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |