| 2015-01-29 15:24:06 | 4TH REVIEW: FBC 2010 |
| | |
| | IN THIS RE-SUBMITTAL, THE APPLICANT HAS PROVIDED A DCA |
| | PLAN MDS007344. THE DCA COVER LETTER WAS NOT PROVIDED, |
| | AND THE PLANS DO NOT HAVE THE DCA STAMP ON THEM. I WAS |
| | UNABLE TO LOCATE THE PLAN ON FLORIDABUILDING.ORG. IT IS |
| | UNCLEAR HOW THIS PLAN RELATES TO THE INSIGNAI |
| | PREVIOUSLY PROVIDED. |
| | |
| | THE PLAN SUBMITTED IS FOR EDUCATIONAL OCCUPANCY; |
| | THEREFORE, THIS HAS BEEN REVIEWED FOR EDUCATIONAL USE |
| | ONLY. PLEASE ADDRESS. NO INFORMATION WAS PROVIDED |
| | REGARDING THE PROPOSED USE OF THIS STRUCTURE. ALTHOUGH |
| | APPLICATION STATES THIS IS "EXISTING" IT IS NOT |
| | CONSIDERED "EXISTING" IF A PERMIT WAS NOT OBTAINED. IT |
| | APPEARS THAT THIS WAS INSTALLED AFTER 2012. |
| | |
| | FROM PREVIOUS LISTS, BE ADVISED THAT THE FOUNDATION |
| | PLAN DOES NOT COMPLY WITH FBC R403.1.4 MINIMUM DEPTH. |
| | ALL EXTERIOR FOOTINGS SHALL BE PLACED AT LEAST 12 |
| | INCHES (305 MM) BELOW THE UNDISTURBED GROUND SURFACE. |
| | NO ADDITIONAL INFORMATION WAS PROVIDED. |
| | |
| | ELECTRICAL IS SHOWN ON THE MODULAR PLAN, AS WELL AS AN |
| | OPTIONAL BATHROOM, BUT NO INFORMATION PROVIDED |
| | REGARDING ELECTRICAL CONNECTION OR PLUMBING CONNECTION |
| | FOR REVIEW. PLANS WILL BE ROUTED FOR ELECTRICAL AND |
| | PLUMBING REVIEWS AFTER THIS INFORMATION IS SUBMITTED. |
| | |
| | FROM PREVIOUS THREE REVIEWS, FBC 109.3 BUILDING PERMIT |
| | VALUATION. FOR PERMITTING PURPOSES, VALUATION OF |
| | BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE |
| | TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, |
| | INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND |
| | DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT; |
| | EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY |
| | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL |
| | CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| | MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE |
| | CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET |
| | BY THE BUILDING OFFICIAL. |
| | |
| | NO IMPACT PROTECTION SHOWN FOR THE MODULAR, PLEASE |
| | ADDRESS FBC 2010 RESIDENTIAL 301.2.1.2, FBC 1609.1.4. |
| | (OCCUPANCY CLASSIFICATION HAS NOT BEEN DETERMINED.) IF |
| | REMOVABLE SHUTTERS ARE PROPOSED, PROVIDE PRODUCT |
| | APPROVALS AND THE SAMPLE INSTALLATION SCHEDULE (OR ALL |
| | INFORMATION IN ANOTHER FORMAT): |
| | |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/SCHEDULE_FOR_INSTALLATION.PDF |
| | |
| | WHEN RESUBMITTING, PLEASE PROVIDE A RESPONSE LETTER |
| | STATING HOW EACH ITEM WAS ADDRESSED (THIS MAY BE DONE |
| | BY CONTRACTOR). ENGINEER IS TO ACKNOWLEDGE RECEIPT OF |
| | THE STRUCTURAL COMMENT. |
| | |