| 2014-12-30 09:31:59 | 3RD REVIEW: FBC 2010 |
| | |
| | IN THIS RE-SUBMITTAL, THE APPLICANT HAS PROVIDED ONLY A |
| | LEGACY DCA INSIGNIA # IVE-002378 FOR THE MODULAR |
| | BUILDING. I COULD NOT LOCATE THE PLAN ON |
| | FLORIDABUILDING.ORG. PLEASE UPDATE THE VALUE OF THE |
| | IMPROVEMENT AND PROVIDE THE PLAN. ADDITIONALLY, BE |
| | ADVISED THAT THE FOUNDATION PLAN DOES NOT COMPLY WITH |
| | FBC R403.1.4 MINIMUM DEPTH. ALL EXTERIOR FOOTINGS SHALL |
| | BE PLACED AT LEAST 12 INCHES (305 MM) BELOW THE |
| | UNDISTURBED GROUND SURFACE. |
| | |
| | THE BELOW COMMENTS FROM THE SECOND REVIEW ARE NOT |
| | ADDRESSED. |
| | |
| | THE SUBMITTED PLAN IS ONLY A FOUNDATION PLAN AND SURVEY |
| | SHOWING AN UNIDENTIFIED 36'X23.5 MODULAR BUILDING. |
| | PROVIDE A PLAN FOR THE BUILDING.PROVIDE ANY OTHER PLANS |
| | SUCH AS ELECTRICAL, PLUMBING, AIR CONDONDITIONING AS |
| | MAY BE NEEDED. |
| | |
| | PROVIDE PLANS PER FBC 107. |
| | |
| | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |