Plan Review Notes
Plan Review Notes For Permit 14080885
Permit Number 14080885
Review Stop B
Sequence Number 2
Notes
Date Text
2014-10-14 11:39:38PLAN REVIEW COMMENTS
  
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. SHEETS C-1 AND
 E-1 ARE REQUIRED TO HAVE THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DRAWING.
  
 2) FBC R301.2.1 SPECIFY THE METHOD OF ATTACHMENT THAT
 WILL BE USED TO INSTALL THE CONCRETE ROOF TILE. IF A
 ROOF TILE ADHESIVE IS USED SUBMIT TWO COPIES OF IT'S
 PRODUCT APPROVALS THAT HAVE BEEN APPROVED IN WRITING BY
 THE DESIGNER OF RECORD. DCA RULE 9N-3 AND FBC 107.3.4.1
  
 3) ON SHEET S-2 THE EXPOSURE CATEGORY IS SPECIFIED AS
 "D" . EXPOSURE CATEGORY "C" IS SPECIFIED ON SHEETS A-1
 AND A-2. THIS STRUCTURE IS LOCATED IN EXPOSURE C, THE
 WINDLOAD PRESSURES ARE INCREASED IN EXPOSURE D. PLEASE
 CORRECT. FBC R301.1.3 AND FBC R301.2.1.4.3
  
 4) THE PLANS INDICATE THAT THE LOCATION OF THE
 SKYLIGHTS IS TO BE DETERMINED ON THE JOB. THE SKYLIGHTS
 HAVE A DESIGN PRESSURE OF +60 PSF, -100 PSF. THEY WILL
 NOT MEET THE UPLIFT PRESSURES OF THE CORNERS (ROOF ZONE
 3) FOR EXPOSURE D. FBC R301.1.3