Plan Review Notes
Plan Review Notes For Permit 14080813
Permit Number 14080813
Review Stop B
Sequence Number 3
Notes
Date Text
2014-12-13 07:43:12BUILDING PLAN REVIEW
 PERMIT: 14081231
 ADD: 5300 EAST AVE.
 CONT: TRILLIUM
 TEL: (561)296-0700
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RDREVIEW/
 DATE: SAT. DEC. 13/2014
 ACTION: DENIED
  
 1) SEMI-COMPLIED. STATE APPROVED MODULAR PLANS
 SUBMITTED.
  
 2) NOTE THIS PERMIT WOULD ALSO BE A CHANGE OF USE
 WITHIN THE SAME OCCUPANCY TYPE, SINCE THE PERMIT
 APPLICATION INDICATES THAT THE BUILDINGS ARE GOING TO
 BE USED FOR CONFERENCE ROOMS AN A3 OCCUPANCY, THE STATE
 APPROVED MODULAR BUILDING WAS RECERTIFIED AS AN A3
 OCCUPANCY, THE USEAGE TO BE LIBRARY READING ROOM.
 PLEASE LOOK AT THE OCCUPANCY DATA, THE OCCUPANY LOAD OF
 26 IS BASED ON THE 2010 FBC-B TABLE 1004.1.1. LIBRARY
 READING ROOMS AT 50 SQ, FT. PER OCCUPANT. 1330 SQ.
 FT./50= 26 OCCUPANTS. TO USE THESE PLANS THE
 MANUFACTURER WOULD BE REQUIRED TO GO BACK TO THE STATE
 AND GET THIS BUILDING RE-CERTIFIED FOR THIS TYPE OF USE
 (A-3 ASSEMBLY FOR A CONFERENCE ROOM OCCUPANCY LOAD
 TAKEN AT 15 SQ. FT. PER OCCUPANT = 87 OCCUPANTS.
  
 THE SITE PLAN INDICATES THE MODULAR BUILDINGS TO BE
 1,200 SQ. FT. OF USEABLE SPACE WITH A MAXIMUM OCCUPANT
 LOAD OF 80 OCCUPANTS WHICH IS CONSISTANT WITH 15 SQ.
 FT. PER OCCUPANT FOR A A3 CONFERANCE ROOM USEAGE.
  
 553.375.RECERTIFICATION OF MANUFACTURED BUILDINGS.PRIOR
 TO THE RELOCATION TO A SITE THAT HAS A HIGHER DESIGN
 WIND SPEED, MODIFICATION, OR CHANGE OF OCCUPANCY OF A
 MANUFACTURED BUILDING WITHIN THE STATE, THE
 MANUFACTURER, DEALER, OR OWNER THEREOF MAY APPLY TO THE
 DEPARTMENT FOR RECERTIFICATION OF THAT MANUFACTURED
 BUILDING. THE DEPARTMENT SHALL, BY RULE, PROVIDE WHAT
 INFORMATION THE APPLICANT MUST SUBMIT FOR
 RECERTIFICATION AND FOR PLAN REVIEW AND INSPECTION OF
 SUCH MANUFACTURED BUILDINGS AND SHALL ESTABLISH FEES
 FOR RECERTIFICATION. UPON A DETERMINATION BY THE
 DEPARTMENT THAT THE MANUFACTURED BUILDING COMPLIES WITH
 THE APPLICABLE BUILDING CODES, THE DEPARTMENT SHALL
 ISSUE A RECERTIFICATION INSIGNIA. A MANUFACTURED
 BUILDING THAT BEARS RECERTIFICATION INSIGNIA DOES NOT
 REQUIRE ANY ADDITIONAL APPROVAL BY AN ENFORCEMENT
 JURISDICTION IN WHICH THE BUILDING IS SOLD OR
 INSTALLED, AND IS CONSIDERED TO COMPLY WITH ALL
 APPLICABLE CODES. AS AN ALTERNATIVE TO RECERTIFICATION
 BY THE DEPARTMENT, THE MANUFACTURER, DEALER, OR OWNER
 OF A MANUFACTURED BUILDING MAY SEEK APPROPRIATE
 PERMITTING AND A CERTIFICATE OF OCCUPANCY FROM THE
 LOCAL JURISDICTION IN ACCORDANCE WITH PROCEDURES
 GENERALLY APPLICABLE UNDER THE FLORIDA BUILDING CODE. .
  
 IN GETTING THE BUILDING RECERTIFIED BY THE STATE IT
 WILL REQUIRE 2 EXITS SINCE THE OCCUPANT LOAD WILL
 REQUIRE 2 EXITS FROM EACH BUILDING AND THE OCCUPANT
 LOAD IS OVER 50 SECTION 2010 FBC-B 1008.1.10 PANIC &
 FIRE HARDWARE. THE EXCEPTION #1 WILL ONLY EXEMPT THE
 MAIN ENTRY/ EXIT FROM PANCI HARDWARE SEE EXEMPTION.
  
 3) THE STATE APPROVED PLANS ALSO INDICATE UNDER THE
 HEADING STRUCTURAL LOAD LIMITATIONS (8) THIS BUILDING
 IS NOT DESIGNED TO BE SUBMERGED IF LOCATED IN A FLOOD
 HAZARD AREA. THIS PROPOSED MANUFACTURED BUILDING WILL
 AS ILLUSTRATED, BE LOCATED IN A "AH" FLOODZONE THE BASE
 FLOOD ELEVATION OF 17'-0" NGVD PLUS AN ADDITIONAL 6
 INCHES OF HEIGHT CITY REQUIREMENT SEE CITY MUIN CODE
 SECTION 94-546. FOR MANUFACTURED BUILDINGS AS WELL AS
 MOBILE HOMES, THIS ELEVATION IS TO THE UNDERSIDE OF THE
 CARRIAGE, NOT FINISH FLOOR. THE STATE APPROVED PLANS
 FOR THE FOUNDATION PAGE DOES NOT INCLUDE THE PRESSURES
 DUE TO MOVING WATER, A ENGINEERED FOUNDATION PLAN WILL
 BE REQUIRED.
  
 ***** NEW COMMENT.*****IMPORTANT!!!!!!!! A MORE
 RESTRICTIVE REQUIEMENT IS FOUND UNDER THE 2010 FBC-B
 1612.4 DESIGN AND CONSTRUCTION. FLOOD HAZARD AREAS
 SHALL BE IN ACCORDANCE WITH CHAPTER 5 OF ASCE 7AND ASCE
 24. WITHIN ASCE 24 TABLE 7-1 REQUIRES FOR A BUILDING
 WITH STRUCTURE CATEGORY II TO BE ABOVE THE BFE (BASE
 FLOOD ELEVATION) + 1FT. OR 18'-0" NGVD TO THE BOTTOM OF
 THE STRUCTURE.
  
 3A) ANY ATTENDANT UTILITES, ELECTRIC & MECHANICAL
 EQUIPMENT WILL NEED TO BE LOCATED ABOVE THE 18'-0" NGVD
 ELEVATION.ASCE 24 TABLE 7-1.
  
 3B) FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF
 ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED IN AN
 "A" FLOOD ZONE. A (3) FLOOD ELEVATION CERTIFICATE WILL
 BE REQUIRED:
 1) TO BE SUBMITTED FOR PERMIT REVIEW FOR THE PROPOSED
 ELEVATION, WITH NOTES!!!!
 2) ONCE THE MANUFACTURED BUILDING IS ISNSTALLED
 3) BEFORE THE ISSUANCE OF C.O. WITH ALL ASSOCIATED
 ELEVATIONS OF ANY ELECTRICAL OR MECHANICAL EQUIPMENT,
 WITH NOTES!!!
  
 FEMA FORM OMB NO. 1660-0008 EXPIRES: JULY 31,2015
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2012, THROUGH JULY 31/ 2015.
 THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL
 SEPTEMBER 30/ 2013. ALTHOUGH THE OLD VERSION OF THE
 FORM IS NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING
 COPIES MAY BE USED UNTIL SEPTEMBER 30/2013. ELEVATIONS
 CERTIFIED ON OR AFTER OCTOBER 1/2013, MUST BE SUBMITTED
 ON THE NEW FORM.
  
 ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW
 FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 4) THE SITE PLAN SUBMITTED HAS AN ENLARGE DETAIL OF THE
 MODULAR BUILDING SITE, THE GRADES AROUND THE BUILDINGS
 HAS NOT BEEN PROVIDED NOR THE FINISH FLOOR HEIGHT OF
 THESE UNITS. SINCE THESE ARE MANUFACTURED BUILDINGS NOT
 DESIGNED TO BE IN FLOOD ZONES THE BOTTOM OF THE FRAMING
 MEMBERS HAVE TO BE ABOVE THE 18'-0" NGVD. THE DETAILS
 FOR WALKWAYS HAVE NOT PROVIDED GRADE ELEVATIONS, PLEASE
 PROVIDE THE GRADE ELEVATIONS AT THE BOTTOM OF THE
 STAIRS AND RAMPS AS WELL AS THE TOP LANDING AND THE
 PROPOSED FINISH FLOOR ELEVATION. ASCE 24 TABLE 7-1.
  
 THE CONCERN IS THE DETAILS SHOW ONLY A 30" RISE. IF THE
 RISE IS GREATER THAN 30 INCHES A MID LANDING WILL NEED
 TO BE INTRODUCE, THIS WILL AFFECT THE LAYOUT OF THE
 RAMP YSTEM. 2010 FBC-ACCESSIBILITY 405.6 RISE MAXIMUM
 OF 30 INCHES.
  
 5A) ALSO OF CONCERN ON THE SITE PLANS, THE STATE
 APPROVED PLANS HAD AN OCCUPANT LOAD OF 26 ONLY
 REQUIRING ONE EXIT, WHEN IN REALITY THE OCCUPANT LOAD
 IS 80 OR MORE WHICH REQUIRES 2 EXITS FROM EACH
 MANUFACTURED BUILDINGS. THE SITE PLAN DOES SHOW A
 SECONDARY EXIT AND RAISED WALKWAY, WHAT THE PLANS DO
 NOT SHOW IS COMPLIANCE WITH 2010 FL ACC. CODE 207.1
 GENERAL. MEANS OF EGRESS SHALL COMPLY WITH SECTION
 1003.2.13 OF THE INTERNATIONAL BUILDING CODE (2000
 EDITION AND 2001 SUPPLEMENT) OR SECTION 1007 OF THE
 INTERNATIONAL BUILDING CODE (2003 EDITION)
 (INCORPORATED BY REFERENCE, SEE ?REFERENCED STANDARDS?
 IN CHAPTER 1).
 2003 IBC-B 1007.1 WHERE MORE THAN ONE EGRESS IS
 REQUIRED BY SECTION 1014.1 OR 1018.1 FROM ANY ACCESIBLE
 SPACE, EACH ACCESSIBLE PORTION OF THE SPACESHALL BE
 SERVED BY NOT LESS THAN 2 ACCESSIBLE MEANS OF EGRESS,
 THIS WILL MEAN AT LEAST 2 RAMPS PER BUILDING OR IF THE
 USE OF A 3RD RAMP IS A COMBINED
 OCCUPANT LOAD SHOW THE MINIMUM REQUIRED WIDTH FOR THE
 COMBINED LOADS.
  
 5B) PLEASE SHOW THE ACCESSIBLE ROUTE FROM THE
 MANUCATRURED BUILDINGS CONNECTING THE REST OF THE
 CAMPUS. 2010 FBC-ACCESS. CODE 206.2.1 & 602.2.2.
  
 6) STRUCTURAL SHEET S-1NOTE ARE ILLEGIBLE PLEASE
 PROVIDE A NEW PLAN, EVEN WHEN YOU ENLARGED PLANS ALSO
 WERE ILLEGIBLE. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED. NOTE HOW WILL THE STAIRS, LANDINGS, RAISED
 WALKWAY AND RAMPS BE ANCHORED FOR COMPLIANCE IN A FLOOD
 ZONE FOR MIGRATING WATERS.
  
 7) THE ENGINEERED FOUNDATIONS FOR THE MANUFACTURED
 BUILDINGS WILL ALSO NEED TO SHOW HOW THEY WILL RESIST
 FLOOD WATERS, THE UNKNOWN AT THIS TIME IS ALSO HOW HIGH
 WILL THE BLOCKS BE STACKED IN A STACKED DRY FOUNDATION?
 1612.5 FLOOD HAZARD DOCUMENTATION.
 THE FOLLOWING DOCUMENTATION SHALL BE PREPARED AND
 SEALED BY A REGISTERED DESIGN PROFESSIONAL AND SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL:
 2.1 THE ELEVATION OF THE BOTTOM OF THE LOWEST
 HORIZONTAL STRUCTURAL MEMBER AS REQUIRED BY THE
 FOUNDATION INSPECTION AND THE FINAL INSPECTION IN
 SECTION 110.3.
 2.2 CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT
 THAT THE BUILDING IS DESIGNED IN ACCORDANCE WITH ASCE
 24, INCLUDING THAT THE PILE OR COLUMN FOUNDATION AND
 BUILDING OR STRUCTURE TO BE ATTACHED THERETO IS
 DESIGNED TO BE ANCHORED TO RESIST FLOTATION, COLLAPSE
 AND LATERAL MOVEMENT DUE TO THE EFFECTS OF WIND AND
 FLOOD LOADS ACTING SIMULTANEOUSLY ON ALL BUILDING
 COMPONENTS, AND OTHER LOAD REQUIREMENTS OF CHAPTER 16.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
 7) ITEMS THAT ARE NOT OF THE STATE APPROVAL ARE GUTTERS
 AND DOWN SPOUTS AND STAIRS, RAMPS AND LANDINGS AND
 FOUNDATIONS. THESE ITEMS WILL NEED PEDDS DOCUMENTS FROM
 THE DESIGNER OF RECORD FOR EACH OF THESE DOCUMENTS.
 NOTE THE STAIRS, RAMPS AND LANDINGS DO NOT SHOW HOW
 THEY ARE GOING TO BE ANCHORED, THESE ARE IN A FLOOD
 ZONE. ALSO NOTE SHEET S-1 NOTES ARE TO SMALL TO READ,
 WILL NOT SCAN. 107.2.1.4 QUALITY OF BUILDING PLANS.
 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS
 FOR PLANS AND SPECIFICATIONS, IN
 ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH
 THE ARCHIVE REQUIREMENTS OF
 FLORIDA STATUTES.
  
 8) PLEASE PROVIDE WHEN THESE BUILDINGS WILL BE OCCUPIED
 START DATE AND END DATE, THE BUILDING CODE DEFINITION
 FOR TEMPORARY IS 180 DAYS, IF LONGER THAN THIS IT IS
 CONSIDERED PERMANENT. MAY NEED TO BE REVIEWED FOR
 IMPACT FEES.
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  