| 2014-10-15 09:48:44 | BUILDING PLAN REVIEW |
| | PERMIT: 14081231 |
| | ADD: 5300 EAST AVE. |
| | CONT: TRILLIUM |
| | TEL: (561)296-0700 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW/ 1ST REVIEW CYCLE |
| | DATE: WED. SEPT. 03/2014 |
| | ACTION: DENIED |
| | |
| | 1) THE SUBMITTED SITE PLAN INDICATE THAT (2) MODULAR |
| | BUILDINGS ARE BEING MOVED ONTO THIS SITE. UNDER THE 1ST |
| | REVIEW REVIEW OF PLANS ARE LOADED UNDER SUPPORTING |
| | DOCUMENTS AND NOT IN THE PLANS SECTION OF THE |
| | PROGRAM!!!!!!!!!!! |
| | |
| | 2) NOTE THIS PERMIT WOULD ALSO BE A CHANGE IN OCCUPANCY |
| | FOR THE MODULAR BUILDINGS SINCE THE PERMIT APPLICATION |
| | INDICATES THEY ARE GOING TO BE USED FOR CONFERENCE |
| | ROOMS, THE STATE APPROVED RECERTIFIED MODULAR BUILDING |
| | WAS RECERTIFIED AS AN EDUCATIONAL OCCUPANCY. THIS MEANS |
| | IT CAN ONLY BE USED FOR KIDS EDUCATION FROM K-12 GRADE. |
| | IF THE MODULAR BUILDINGS ARE BEING USED AS CONFERENCE |
| | ROOMS THE FLOOR LOADING CHANGES. IF THE USAGE AS A |
| | CONFERENCE ROOM IS NOT FOR CHILDREN K-12 GRADE THEN THE |
| | CHANGE OF OCCUPANCY WILL BE AN A3 OCCUPANCY. THE FLOOR |
| | LOADING WILL BE 60 PSF IF SEATS ARE FASTENED IN PLACE |
| | (FROM FACTORY) OTHERWISE THE FLOOR LOADING WILL BE 100 |
| | PSF. |
| | |
| | 3) THE OTHER ISSUE THAT WE WILL HAVE IS WITH A OCCUPANT |
| | LOAD OF 50 OR GREATER FOR AN ASSEMBY OCCUPANCY |
| | 1008.1.10 WILL REQUIRE PANIC BAR |
| | HARDWARE. |
| | |
| | 4) STATE APPROVED MODULAR BUILDING PLANS ARE NORMALLY |
| | STATE REVIEWED WITH A BUSINESS OCCUPANCY,THE ORIGINAL |
| | PLANS UNDER THE 2001 FBC-B WERE A BUSINESS OCCUPANCY. |
| | TWERE RE-ISSUED UNDER THE 2010 FBC-B AS EDUCATUIONAL, |
| | IF NOT SERVING CHILDREN BETWEEN THE GRADES K-12TH GRADE |
| | THEY WILL NEED A REVISION TO THE STATE TO BE |
| | RECERTIFIED AS A A-3 OCCUPANCY. 2010 FBC-EXISTING |
| | BUILDING CODE 901.3. |
| | |
| | 5) 553.375.RECERTIFICATION OF MANUFACTURED |
| | BUILDINGS.PRIOR TO THE RELOCATION TO A SITE THAT HAS A |
| | HIGHER DESIGN WIND SPEED, MODIFICATION, OR CHANGE OF |
| | OCCUPANCY OF A MANUFACTURED BUILDING WITHIN THE STATE, |
| | THE MANUFACTURER, DEALER, OR OWNER THEREOF MAY APPLY TO |
| | THE DEPARTMENT FOR RECERTIFICATION OF THAT MANUFACTURED |
| | BUILDING. THE DEPARTMENT SHALL, BY RULE, PROVIDE WHAT |
| | INFORMATION THE APPLICANT MUST SUBMIT FOR |
| | RECERTIFICATION AND FOR PLAN REVIEW AND INSPECTION OF |
| | SUCH MANUFACTURED BUILDINGS AND SHALL ESTABLISH FEES |
| | FOR RECERTIFICATION. UPON A DETERMINATION BY THE |
| | DEPARTMENT THAT THE MANUFACTURED BUILDING COMPLIES WITH |
| | THE APPLICABLE BUILDING CODES, THE DEPARTMENT SHALL |
| | ISSUE A RECERTIFICATION INSIGNIA. A MANUFACTURED |
| | BUILDING THAT BEARS RECERTIFICATION INSIGNIA DOES NOT |
| | REQUIRE ANY ADDITIONAL APPROVAL BY AN ENFORCEMENT |
| | JURISDICTION IN WHICH THE BUILDING IS SOLD OR |
| | INSTALLED, AND IS CONSIDERED TO COMPLY WITH ALL |
| | APPLICABLE CODES. AS AN ALTERNATIVE TO RECERTIFICATION |
| | BY THE DEPARTMENT, THE MANUFACTURER, DEALER, OR OWNER |
| | OF A MANUFACTURED BUILDING MAY SEEK APPROPRIATE |
| | PERMITTING AND A CERTIFICATE OF OCCUPANCY FROM THE |
| | LOCAL JURISDICTION IN ACCORDANCE WITH PROCEDURES |
| | GENERALLY APPLICABLE UNDER THE FLORIDA BUILDING CODE. |
| | |
| | 6) THE STATE APPROVED PLANS ALSO INDICATE UNDER THE |
| | HEADING STRUCTURAL LOAD LIMITATIONS (8) THIS BUILDING |
| | IS NOT DESIGNED TO BE SUBMERGED IF LOCATED IN A FLOOD |
| | HAZARD AREA. THIS PROPOSED MANUFACTURED BUILDING WILL |
| | AS ILLUSTRATED, BE LOCATED IN A "AH" FLOODZONE THE BASE |
| | FLOOD ELEVATION OF 17'-0" NGVD PLUS AN ADDITIONAL 6 |
| | INCHES OF HEIGHT CITY REQUIREMENT SEE CITY MUIN CODE |
| | SECTION 94-546. FOR MANUFACTURED BUILDINGS AS WELL AS |
| | MOBILE HOMES, THIS ELEVATION IS TO THE UNDERSIDE OF THE |
| | CARRIAGE, NOT FINISH FLOOR. THE STATE APPROVED PLANS |
| | FOR THE FOUNDATION PAGE DOES NOT INCLUDE THE PRESSURES |
| | DUE TO MOVING WATER, A ENGINEERED FOUNDATION PLAN WILL |
| | BE REQUIRED. |
| | |
| | 6A) ANY ATTENDANT UTILITES, ELECTRIC & MECHANICAL |
| | EQUIPMENT WILL NEED TO BE LOCATED ABOVE THE 17'-6" NGVD |
| | ELEVATION. CITY MUNI CODE 94-546 . |
| | |
| | 6B) FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF |
| | ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED IN AN |
| | "A" FLOOD ZONE. A (3) FLOOD ELEVATION CERTIFICATE WILL |
| | BE REQUIRED: |
| | 1) TO BE SUBMITTED FOR PERMIT REVIEW FOR THE PROPOSED |
| | ELEVATION, WITH NOTES!!!! |
| | 2) ONCE THE MANUFACTURED BUILDING IS ISNSTALLED |
| | 3) BEFORE THE ISSUANCE OF C.O. WITH ALL ASSOCIATED |
| | ELEVATIONS OF ANY ELECTRICAL OR MECHANICAL EQUIPMENT, |
| | WITH NOTES!!! |
| | |
| | FEMA FORM OMB NO. 1660-0008 EXPIRES: JULY 31,2015 |
| | FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR |
| | USE, EFFECTIVE AUGUST 1/ 2012, THROUGH JULY 31/ 2015. |
| | THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL |
| | SEPTEMBER 30/ 2013. ALTHOUGH THE OLD VERSION OF THE |
| | FORM IS NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING |
| | COPIES MAY BE USED UNTIL SEPTEMBER 30/2013. ELEVATIONS |
| | CERTIFIED ON OR AFTER OCTOBER 1/2013, MUST BE SUBMITTED |
| | ON THE NEW FORM. |
| | |
| | ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW |
| | FORM, AND INSTRUCTIONS ARE AVAILABLE AT: |
| | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| | |
| | 7) ITEMS THAT ARE NOT OF THE STATE APPROVAL ARE GUTTERS |
| | AND DOWN SPOUTS AND STAIRS, RAMPS AND LANDINGS AND |
| | FOUNDATIONS. THESE ITEMS WILL NEED PEDDS DOCUMENTS FROM |
| | THE DESIGNER OF RECORD FOR EACH OF THESE DOCUMENTS. |
| | NOTE THE STAIRS, RAMPS AND LANDINGS DO NOT SHOW HOW |
| | THEY ARE GOING TO BE ANCHORED, THESE ARE IN A FLOOD |
| | ZONE. ALSO NOTE SHEET S-1 NOTES ARE TO SMALL TO READ, |
| | WILL NOT SCAN. 107.2.1.4 QUALITY OF BUILDING PLANS. |
| | BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH |
| | SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE |
| | MEDIUM. THE BUILDING OFFICIAL MAY |
| | ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS |
| | FOR PLANS AND SPECIFICATIONS, IN |
| | ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION |
| | PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| | OTHER ITEMS RELATED TO RECORDS |
| | MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH |
| | THE ARCHIVE REQUIREMENTS OF |
| | FLORIDA STATUTES. |
| | |
| | 8) PLEASE PROVIDE WHEN THESE BUILDINGS WILL BE OCCUPIED |
| | START DATE AND END DATE, THE BUILDING CODE DEFINITION |
| | FOR TEMPORARY IS 180 DAYS, IF LONGER THAN THIS IT IS |
| | CONSIDERED PERMANENT. MAY NEED TO BE REVIEWED FOR |
| | IMPACT FEES. |
| | |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |