Notes
Date Text
2014-09-15 09:38:061) INDICATE THE OCCUPANT LOAD FOR EACH MODULAR BUILDING
 PER TABLE 1004.1.1 OF 2010 FBC.
 2) INDICATE ON THE PLAN HOW THE OCCUPANTS WILL HAVE
 ACCESS TO THE REQUIRED SANITARY FACILITIES PER TABLE
 403.1 OF THE 2010 FL. PLUMBING CODE. FACILITIES SHALL
 BE PROVIDIED FOR EACH SEX.FPC SEC.403.2.
 3) THE PATH OF TRAVEL TO SANITARY FACILITIES SHALL NOT
 EXCEED 500 FEET PER THE FPC SEC.403.3.2.
 4) LOCATION OF THE SANITARY FACILITIES SHALL BE CLEARLY
 DESIGNATED BY SIGNAGE COMPLYING WITH THE 2010 FPC
 SEC.403.4, 403.4.1.
 5) ALL ROUTES PROVIDING ACCESS TO THE SANITARY
 FACILITIES SHALL COMPLY W/ THE FLORIDA ACCESSIBILITY
 CODE, ACCESSIBILITY.
 6) THE PLANS SHOW AN OPTIONAL RESTROOM INSIDE THE
 BUILDING. IF THIS RESTROOM WILL BE FURNISHED, SUPPLY
 DETAILS ON THE WATER AND SEWER CONNECTIONS TO THESE
 BUILDINGS. THE WATER CONNECTION SHALL BE PROVIDED W/ A
 BACKFLOW PREVENTER.