Plan Review Notes
Plan Review Notes For Permit 14080813
Permit Number 14080813
Review Stop B
Sequence Number 1
Notes
Date Text
2014-09-03 16:08:50BUILDING PLAN REVIEW
 PERMIT: 14081231
 ADD: 5300 EAST AVE.
 CONT: TRILLIUM
 TEL: (561)296-0700
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. SEPT. 03/2014
 ACTION: DENIED
  
 1) THE SUBMITTED SITE PLAN INDICATE THAT (2) MODULAR
 BUILDINGS ARE BEING MOVED ONTO THIS SITE. NO PLANS FOR
 THE UNITS WERE SUBMITTED. IF THEY ARE STATE APPROVED
 MODULAR BUILDINGS, THEN WE STILL NEED THE PLANS, THEY
 ARE NOT REQUIRED TO BE SIGNED AND SEALED BUT THEY WILL
 BE REQUIRED
 TO HAVE THE APPROVED AGENCY STAMP ON THE PLANS.
  
 2) NOTE THIS PERMIT WOULD ALSO BE A CHANGE IN OCCUPANCY
 FOR THE MODULAR BUILDINGS SINCE THE PERMIT APPLICATION
 INDICATES THEY ARE GOING TO BE USED FOR CONFERENCE
 ROOMS, THE SITE PLAN INDICATES BOTH BUILDINGS ARE OVER
 750 SQ FT WHICH WOULD PUT THE OCCUPANT LOAD OF 50 OR
 GREATER OCCUPANTS REQUIRING (2) MEANS OF EGRESS. 2010
 FBC-B 1015.1.
  
 3) THE OTHER ISSUE THAT WE WILL HAVE IS WITH A OCCUPANT
 LOAD OF 50 OR GREATER FOR AN ASSEMBY OCCUPANCY
 1008.1.10 WILL REQUIRE PANIC BAR
 HARDWARE.
  
 4) STATE APPROVED MODULAR BUILDING PLANS ARE NORMALLY
 STATE REVIEWED WITH A BUSINESS OCCUPANCY, THEY WOULD
 NEED TO GO BACK TO THE ISSUEING AGENCY AND GET A
 REVISION TO THE STATE APPROVED PLANS FOR THE NEW A3
 OCCUPANCY.
  
 5) THIS IS A UNKNOWN AT THIS TIME.
 553.375.RECERTIFICATION OF MANUFACTURED BUILDINGS.PRIOR
 TO THE RELOCATION TO A SITE THAT HAS A HIGHER DESIGN
 WIND SPEED, MODIFICATION, OR CHANGE OF OCCUPANCY OF A
 MANUFACTURED BUILDING WITHIN THE STATE, THE
 MANUFACTURER, DEALER, OR OWNER THEREOF MAY APPLY TO THE
 DEPARTMENT FOR RECERTIFICATION OF THAT MANUFACTURED
 BUILDING. THE DEPARTMENT SHALL, BY RULE, PROVIDE WHAT
 INFORMATION THE APPLICANT MUST SUBMIT FOR
 RECERTIFICATION AND FOR PLAN REVIEW AND INSPECTION OF
 SUCH MANUFACTURED BUILDINGS AND SHALL ESTABLISH FEES
 FOR RECERTIFICATION. UPON A DETERMINATION BY THE
 DEPARTMENT THAT THE MANUFACTURED BUILDING COMPLIES WITH
 THE APPLICABLE BUILDING CODES, THE DEPARTMENT SHALL
 ISSUE A RECERTIFICATION INSIGNIA. A MANUFACTURED
 BUILDING THAT BEARS RECERTIFICATION INSIGNIA DOES NOT
 REQUIRE ANY ADDITIONAL APPROVAL BY AN ENFORCEMENT
 JURISDICTION IN WHICH THE BUILDING IS SOLD OR
 INSTALLED, AND IS CONSIDERED TO COMPLY WITH ALL
 APPLICABLE CODES. AS AN ALTERNATIVE TO RECERTIFICATION
 BY THE DEPARTMENT, THE MANUFACTURER, DEALER, OR OWNER
 OF A MANUFACTURED BUILDING MAY SEEK APPROPRIATE
 PERMITTING AND A CERTIFICATE OF OCCUPANCY FROM THE
 LOCAL JURISDICTION IN ACCORDANCE WITH PROCEDURES
 GENERALLY APPLICABLE UNDER THE FLORIDA BUILDING CODE.
  
 6) THE STATE APPROVED PLANS ALSO INDICATE UNDERTHE
 HEADING STRUCTURAL LOAD LIMITATIONS (8) THIS BUILDING
 IS NOT DESIGNED TO BE SUBMERGED IF LOCATED IN A FLOOD
 HAZARD AREA. THIS PROPOSED MANUFACTURED BUILDING WILL
 AS ILLUSTRATED, BE LOCATED IN A "AH" FLOODZONE THE BASE
 FLOOD ELEVATION OF 17'-0" NGVD PLUS AN ADDITIONAL 6
 INCHES OF HEIGHT CITY REQUIREMENT SEE CITY MUIN CODE
 SECTION 94-546. FOR MANUFACTURED BUILDINGS AS WELL AS
 MOBILE HOMES, THIS ELEVATION IS TO THE UNDERSIDE OF THE
 CARRIAGE, NOT FINISH FLOOR. THE STATE APPROVED PLANS
 FOR THE FOUNDATION PAGE DOES NOT INCLUDE THE PRESSURES
 DUE TO MOVING WATER, A ENGINEERED FOUNDATION PLAN WILL
 BE REQUIRED.
  
 6A) ANY ATTENDANT UTILITES, ELECTRIC & MECHANICAL
 EQUIPMENT WILL NEED TO BE LOCATED ABOVE THE 17'-6" NGVD
 ELEVATION. CITY MUNI CODE 94-546 .
  
 6B) FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF
 ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED IN AN
 "A" FLOOD ZONE. A (3) FLOOD ELEVATION CERTIFICATE WILL
 BE REQUIRED:
 1) TO BE SUBMITTED FOR PERMIT REVIEW FOR THE PROPOSED
 ELEVATION, WITH NOTES!!!!
 2) ONCE THE MANUFACTURED BUILDING IS ISNSTALLED
 3) BEFORE THE ISSUANCE OF C.O. WITH ALL ASSOCIATED
 ELEVATIONS OF ANY ELECTRICAL OR MECHANICAL EQUIPMENT,
 WITH NOTES!!!
  
 FEMA FORM OMB NO. 1660-0008 EXPIRES: JULY 31,2015
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2012, THROUGH JULY 31/ 2015.
 THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL
 SEPTEMBER 30/ 2013. ALTHOUGH THE OLD VERSION OF THE
 FORM IS NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING
 COPIES MAY BE USED UNTIL SEPTEMBER 30/2013. ELEVATIONS
 CERTIFIED ON OR AFTER OCTOBER 1/2013, MUST BE SUBMITTED
 ON THE NEW FORM.
  
 ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW
 FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  