| 2014-08-28 07:55:23 | DATE: 8/28/2014 |
| | PROJECT: HOSPICE OF PALM BEACH |
| | PERMIT#: 14080809 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: PROVISO |
| | |
| | 1) FBC-ENERGY |
| | 505.2 LIGHTING CONTROLS (MANDATORY). |
| | LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS |
| | REQUIRED IN SECTIONS 505.2.1, 505.2.2, 505.2.3 AND |
| | 505.2.4. |
| | |
| | 2) NEC 600.5 |
| | EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS |
| | SHALL BE PROVIDED WITH AT LEAST ONE OUTLET SUPPLIED BY |
| | A BRANCH CIRCUIT RATED AT LEAST 20 AMPERES THAT |
| | SUPPLIES NO OTHER LOAD. |
| | |
| | 3) ALL EXTERIOR LIGHTING ( INCLUDING SIGNS AND LED |
| | ACCENT LIGHTING) NOT EXEMPTED BY FBC 505.1 SHALL HAVE |
| | AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN NOT |
| | REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME CLOCK OR |
| | ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES SHALL BE |
| | CAPABLE OF RETAINING PROGRAMING DURING A LOSS OF POWER |
| | FOR A MINIMUM OF 10 HOURS. FBC-E 505.2.4 |
| | |
| | 4) PROVIDE A PANEL SCHEDULE INDICATING THE AVAILABLE |
| | CIRCUITS FOR THE PROJECT. INDICATE THE CIRCUITING ON |
| | THE SITE PLAN. WPB FBC 107.2.1 |
| | |
| | 5) INDICATE LOCATIONS AND PROVIDE ACCESS FOR REMOTE |
| | DRIVERS. |
| | |
| | 6) LISTING AND LABELING OF EQUIPMENT IS REQUIRED BY AN |
| | APPROVED TESTING LAB. IN JUDGING EQUIPMENT, |
| | CONSIDERATION SUCH AS THE FOLLOWING SHALL BE EVALUATED: |
| | SUITABILITY FOR INSTALLATION AND USE IN CONFORMITY WITH |
| | THE PROVISIONS OF THIS CODE. NEC 110.3(A)(1 THRU 8) |
| | |