| Date |
Text |
| 2014-08-22 08:34:47 | DATE: 8/19/2014 |
| | PROJECT: HOPKINS MARINE |
| | PERMIT#: 14050989, REVISION TRACKING #14080802 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 2ND ELECTRICAL PLAN REVIEW, REVISION TRACKING #14080802 |
| | ACTION: DENIED |
| | |
| | 1)EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED |
| | MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND |
| | ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE |
| | REQUIRED ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL |
| | BE DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY |
| | INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF |
| | A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT |
| | REQUIRES EMERGENCY ILLUMINATION. NEC 700.16 |
| | REVISE PLANS TO INDICATE COMPLIANCE WITH NEC 700.16 |
| | |
| | 2) PROVIDE WIND LOAD CALCULATIONS FOR POLE LIGHT IN THE |
| | PARKING LOT. |
| | |
| | 3) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, PLANS, AND SHOP |
| | DRAWINGS AS REQUIRED FOR CCTV, DATA/COM, NETWORK, |
| | AUDIO/VIDEO, AND SIGNAGE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT |
| | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| | ITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |