| 2014-08-26 15:35:59 | DATE: 8/26/2014 | | | PROJECT: POTTER | | | PERMIT#: 14080799 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 2ND ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | DUPLICATE COMMENTS: | | | 1) PROVIDE A SITE PLAN TO INDICATE THE LOCATION OF THE | | | ELECTRICAL PANEL TO BE CHANGED TO ILLUSTRATE THE | | | REQUIRED SERVICE ENTRANCE OVER CURRENT PROTECTIVE | | | DEVICE AS PER NEC 230.91 LOCATION. | | | REVISE THE RISER DIAGRAM TO INDICATE THE LOCATION OF | | | THE MAIN DISCONNECT (SERVICE OCPD) | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT | | | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM | | | ITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | | SHEETS FOR COMPARATIVE REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] |
|