| 2014-08-21 12:15:35 | DATE: 8/21/2014 | | | PROJECT: CAFE TOSCANO | | | PERMIT#: 13101093, REVISION #14080745 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 1ST ELECTRICAL PLAN REVIEW: REVISION #14080745 | | | ACTION: PROVISO | | | | | | 1) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL | | | BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL | | | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL | | | SWITCHES. THE BRANCH CIRCUIT THAT FEEDS UNIT EQUIPMENT | | | SHALL BE CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL. | | | EMERGENCY LUMINAIRES THAT OBTAIN POWER FROM A UNIT | | | EQUIPMENT AND ARE NOT PART OF THE UNIT EQUIPMENT SHALL | | | BE WIRED TO THE UNIT EQUIPMENT AS REQUIRED BY 700.9 AND | | | BY ONE OF THE WIRING METHODS OF CHAPTER 3. NEC | | | 700.12(F) | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|