| Plan Review Notes For Permit 14080705 |
| Permit Number |
14080705 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-03 12:31:31 | 14080705 | | | 6001 VILLAGE BLVD. | | | STORAGE UNITS | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | SHOW LOCATION OF THE ELECTRICAL SERVICE AND SERVICE | | | DISCONNECTS. NEC 215.5 | | | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | | FOR THE ELECTRIC SERVICE, PANEL BOARDS AND MAIN | | | DISCONNECTING MEANS. NEC 110.16, 110.22 | | | | | | VERIFY THE ELECTRICAL DISCONNECTING MEANS AND PANEL | | | BOARDS HAVE A FAULT CURRENT RATING THAT IS SUFFICIENT | | | AT NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE | | | INTERRUPTED. INDICATE THE MAXIMUM AVAILABLE FAULT | | | CURRENT AT THE SERVICE POINT FROM THE ELECTRICAL | | | UTILITY. NEC 110.9, 110.10 | | | | | | PROVIDE DEDICATED EQUIPMENT SPACES WITH SAFE WORKING | | | CLEARANCE AND DIMENSIONS FOR THE MAIN DISCONNECTS AND | | | PANEL BOARDS. NEC 110.26 | | | | | | | | | ROBERT LECKY, CBO | | | ELECTRICAL PLANS REVIEW | | | 561-373-3701 | | | [email protected] | | | |
|