Plan Review Notes
Plan Review Notes For Permit 14080705
Permit Number 14080705
Review Stop B
Sequence Number 1
Notes
Date Text
2014-08-30 13:41:18BUILDING PLAN REVIEW
 PERMIT: 14080705
 ADD: 6001 VILLAGE BLVD
 CONT: BRYAN MCINTURE
 TEL: (561)745-2858
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. AUG. 30/ 2014
 ACTION: DENIED
  
 1) THERE IS NO SITE PLAN SHOWING THE PLACEMENT OF THESE
 UNITS, NEITHER DOES THE SUBMITTED SURVEY INDICATE THE
 LOCATION WHERE THESE UNITS WILL BE INSTALLED.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS. THE EXAMINATION OF THE
 DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE
 FOLLOWING MINIMUM CRITERIA AND DOCUMENTS: A FLOOR PLAN;
 SITE PLAN; FOUNDATION PLAN AND ALL EXTERIOR ELEVATIONS:
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES AND, AS APPLICABLE,
 FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN FLOOD
 ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN
 ACCURATE BOUNDARY LINE SURVEY.
  
 2) THIS PROPERTY IS LOCATED WITHIN A FLOOD ZONE. FBC
 BUILDING 3110.1.2 / CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A8" FLOOD
 ZONE MINIMUM SLAB ELEVATION IS 15.5 FT NGVD. A FLOOD
 ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE REVIEW
 CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE AN
 ADDITIONAL 6 INCHES OF ELEVATION.
  
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANT
 A/C PADS OR OTHER SLABS FOR GENERATORS
  
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31,2015
  
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015.
 FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE
 NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 3) THIS PLAN IS NOT A STATE APPROVED PLAN, PLEASE
 PROVIDE COMPLIANCE WITH 2010 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) ROOFING PRODUCTS AND ASSEMBLIES
 (D) SHUTTERS
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  