| 2014-12-22 08:18:06 | BUILDING PLAN REVIEW |
| | PERMIT: 14080632 |
| | ADD: 500 BELVEDERE RD. |
| | CONT: T. B. D. |
| | TEL: (216)520-1551 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: MON. DEC. 22/ 2014 |
| | ACTION: BUILDING PROVISO |
| | |
| | CONTRACTOR IS WORKING AT OWN RISK. SHEET S001 |
| | FOUNDATION NOTES INDICATE A SOILS REPORT IS REQUIRED. |
| | IT SHALL BE THE RESPONSIBILITY OF THE SOILS TESTING |
| | LABORATORY TO VERIFY THE ASSUMED BEARING PRESSURE . |
| | 2010 FBC-B 1803.5.2 QUESTIONABLE SOIL. |
| | WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY |
| | OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE |
| | SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE |
| | BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| | GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| | 1) |
| | |
| | 2) SHEET S001 THE COMPONETS AND CLADDING CHART FOR ROOF |
| | ZONE 3, THE PRESSURES ARE THE SAME AS ZONE # 2, THESE |
| | PRESSURES ARE OK FOR THE ROOF ZONE # 3 BEHIND A 3'-0" |
| | PARAPET AT THE HEIGHT OF 22 FT. A REVISION IS REQUIRED |
| | SHOWING THE PRESSURES FOR THE ELEVATION 35 FT WHERE |
| | THERE IS NO PARAPET AND INCREASED PRESSURES. 2010 FBC-B |
| | 1609.6. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |