Plan Review Notes
Plan Review Notes For Permit 14080632
Permit Number 14080632
Review Stop B
Sequence Number 2
Notes
Date Text
2014-11-13 12:30:55BUILDING PLAN REVIEW
 PERMIT: 14080632
 ADD: 500 BELVEDERE RD.
 CONT: T. B. D.
 TEL: (216)520-1551
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. NOV. 13/ 2014
 ACTION: DENIED
  
 PLEASE TAKE NOTE!!!!
 NOTICE:
 CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES THAT A
 LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE
 FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED (3) OR MORE
 TIMES FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION.
 THIS IS TO BE PAID BY THE DESIGN TEAMS!!!!.
  
  
  
 2ND REQUEST , ORIGINAL SHEETS ARE STILL IN PLANS,
 RESPONSE COMMENTS START AT COMMENT # 4.
 1) THE COVERSHEET INDICATES THIS BUILDING WAS DESIGNED
 AS A TYPE LLB BUILDING. HOW CAN THE EXISTING BUILDING
 BE A TYPE LLB BUILDING WHEN THE 2010 FBC-B 603.1
 ALLOWABLE MATERIALS. COMBUSTIBLE MATERIALS SHALL BE
 PERMITTED IN BUILDINGS OF TYPE I OR II CONSTRUCTION IN
 THE FOLLOWING APPLICATIONS AND IN ACCORDANCE WITH
 SECTIONS 603.1.1 THROUGH 603.1.3:
 1. FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN:
 1.3. ROOF CONSTRUCTION, INCLUDING GIRDERS, TRUSSES,
 FRAMING AND DECKING.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 SHEET S301 ALSO SHOWS EXISTING WOOD FRAMING MEMBERS AND
 SHEATHING DETAILS 2A, 2B AND CANOPY ROOF PLAN SHOW THE
 USSE OF NEW 3/4 INCH WOOD DECKING . THE EXISITNG
 BUILDING CODE SECTION 1001.2 CREATION OR EXTENSION OF
 NONCONFORMITY.
 AN ADDITION SHALL NOT CREATE OR EXTEND ANY
 NONCONFORMITY IN THE EXISTING BUILDING TO WHICH THE
 ADDITION IS BEING MADE WITH REGARD TO ACCESSIBILITY,
 STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR
 THE CAPACITY OF MECHANICAL, PLUMBING, OR ELECTRICAL
 SYSTEMS.
  
 2) 2ND REQUEST. MISSING PRODUCT APPROVALS: 2010 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS
 & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) ACCESS DOOR IN CEILING A NORSTRUM CEILING
 APPROVAL HAS BEEN SUBMITTED. THE APPROVAL NEEDS TO BE A
 MIAMI-DADE NOA OR A STATE OF FLORIDA APPROVAL,
 OTHERWISE NORSTORM WILL NEED TO SUBMIT FOR A LOCAL
 APPROVAL.
 (C) COMPIED. EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, SUBMITTED IS A
 FLORIDA APPROVAL FOR CARLISLE SURE WELD TPO SINGLE PLY
 ROOF SYSTEM, THE COVER SHEET OF THE PLANS LIST PAGE 6
 OF THIS REPORT FOR ATTACHMENT METHOD. PLEASE BE AWARE
 THERE IS 8 SUB-SYSTEMS FOUND ON PAGE 6. PLEASE IDENTIFY
 WHICH SUB-SYSTEM IS TO BE INSTALLED. EACH SUB-SYSTEM
 HAS DIFFERENT PRESSURES FOR ZONE # 1 AND MAY OR MAY NOT
 MEET THE WIND DESIGN PRESSURES.
  
 3) 2ND REQUEST, SUB-SYSTEMS NOT IDENTIFIED. 2010 FBC
 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) 2ND REQUEST. SHEET S-001 UNDER THE HEADING OF WIND
 DESIGN DATA:
 MWFRS DESIGN PRESSURES- BUILDING DESIGN BY PUBLIX
 COMPONENTS & CLADDING DESIGN PRESSURES IN VULT
 WIND PRESSURES FOR ZONES 4 & 5 (WALL ZONES)
 PRESSURES ARE LOW FOR WALL ZONE 4
 PRESSURES ARE HIGH FOR WALL ZONE 5 @ 190 MPH.
  
 COMMENT BELOW CHART.
 NOTE. WIND LOADS FOR COMPONENTS AND CLADDING SHALL
 CONFORM TO THE FBC CRITERIA. THE CLADDING SUPPLIERS
 SHALL CONSIDER SHALL CONSIDER INCREASED PRESSURE
 COEFFICIENTS FOR THE COMPONENTS AND CLADDING AND
 DETERMINE THE APPROPRIATE WIND LOADS FOR THIER SYSTEMS
 BASED ON ZONE, HEIGTH AND EFFECTIVE WIND AREA.
  
 THE PRESSURES FOR BOTH ZONES 4 & 5 (WALL ZONES) SHOULD
 ALREADY REFLECT THE CORRECT PRESSURES FOR HEIGHT AND
 EXPOSURE. THE PRESSUES MUST MEET THE MINIMUM PRESSURES
 REQUIRED FOR THE WIND ZONE, EXPOSURE AND HEIGHT OF THE
 BUILDING. THE PRESSURES WILL NEED TO BE CORRECTED FOR
 WALL ZONE 4. IF THE DESIGNER OF RECORD DESIGNS TO A
 HIGHER PRESSURE (WALL ZONE #5) THAT IS WHAT THE PRODUCT
 APPROVALS HAVE TO MEET.
  
 PLEASE ALSO NOTE THAT SHEET S001 IN THE TITLE STRIP
 LISST THIS SHEET AS PUBLIX SUPPLEMENTAL DOCUMENTS. AS
 DISCUSSED WITH CMG ARCHITECTS THIS MORNING
 IT APPEARS THE THE PUBLIX ARCHITECTS SHOULS BE THE
 DESIGNER OF RECORD FOR PUBLIX. THE ISSUE HERE IS PUBLIX
 HAS NOTHING TO DO WITH THE REST OF THE SHOPPING CENTER.
 THE PUBLIX PERMIT IS THE NEW PUBLIX STORE AND CANOPY.
 THERE SHOULD BE A 3 HOUR WALL THAT SEPARATES THE PUBLIX
 STORE FROM THE REMAINDER OF THE SHOPPING CENTER. ON
 THESE PLANS OMIT THE PORTION THAT DEALS WITHPUBLIX/
 UNDER SEPARATE PERMIT. THIS SHOULD BE A STAND ALONE
 PERMIT THAT HAS NOTHING TO DO WITH PUBLIX, UNLESS THEY
 ARE GOING TO BECOME THE DESIGNER OF RECORD FOR THE
 WHOLE OF THE SHOPPING CENTER.
 FLORIDA STATUTE 61G1-23.015 RESPONSIBLE SUPERVISING
 CONTROL OVER ARCHITECTURAL PRACTICE OUTSIDE OF THE
 ARCHITECT?S OFFICE.
  
 THE OTHER ISSUE WITH THIS PAGE IS THE STATEMENT UNDER
 GENERAL:
 THE ADDED STRUCTURE AS SHOWN ON THESE DRAWINGS TO THE
 BUILDING IS DESIGNED TO BE SELF SUPPORTING AND STABLE
 AFTER CONSTRUCTION IS FULLY COMPLETED.
 AGAIN THIS TO BE CONSIDERED A ADDITION TO AN EXISTING
 BUILDING. THE DESIGN CRITERIA LIST THIS AS A TYPE IIB
 BUILDING SHEET A302, A303 & A304 ALL STILL LIST THE USE
 OF EXISTING 5/8 IN. EXTERIOR GRADE PLYWOOD, AND SHEET
 A304 STILL LIST WOOD TRUSSES TO BE MODIFIEDFOR NEW
 METAL STUD ATTACHMENT.
 PLEASE REVIEW: 2010 EXISTING BUILDING CODE 1001.2
 CREATION OR EXTENSION OF NONCONFORMITY.
 AN ADDITION SHALL NOT CREATE OR EXTEND ANY
 NONCONFORMITY IN THE EXISTING BUILDING TO WHICH THE
 ADDITION IS BEING MADE WITH REGARD TO ACCESSIBILITY,
 STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR
 THE CAPACITY OF MECHANICAL, PLUMBING, OR ELECTRICAL
 SYSTEMS.
  
 PLEASE ALSO NOT THERE ARE NO ROOFING PRESSURES PROVIDED
 FOR ZONES 1, 2 OR 3.
  
 PLEASE PROVIDE FOR ALL ZONES 1-5 THE PRESSURES IN VASD
 SINCE ALL THE PRODUCT APPROVALS ARE STATED IN VASD.
  
 1ST REVIEW: MISSING THE PRESSURES AND WIND DESIGN FOR
 PRODUCT APPROVALS. 2010 FBC-B 1609.1.1 DETERMINATION OF
 WIND DESIGN- CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 4.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 4.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 5) 2ND REQUEST, THIS SHEET REFERS BACK TO SOILS TESTING
 FOR THE PUBLIX BUILDING. SHEET S001 FOUNDATION NOTES
 INDICATE A SOILS REPORT IS REQUIRED. 1803.5.2
 QUESTIONABLE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  