2014-09-03 11:20:4914080632
 500 BELVEDERE ROAD.
 CANOPY AND SITE LIGHTING
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE AN ELECTRICAL RISER PLAN OF THE ELECTRICAL
 SERVICE SHOWING LOCATION OF ALL METERS AND MAIN
 DISCONNECTS. VERIFY THE ELECTRICAL SERVICE MAINS
 SERVING THIS BUILDING ARE SIX OR LESS AND GROUPED IN
 ONE LOCATION. VERIFY THE FAULT CURRENT RATING OF THE
 NEW EQUIPMENT IS SUITABLE. NOTE THAT THE PLANS SHOW THE
 LIGHTING PANELS AS BEING EXISTING ON ONE SHEET AND NEW
 ON ANOTHER. NEC 110.9, 110.10, 110.26, 215.5, 230.71,
 240.24(D)
  
 PROVIDE WIND LOAD ENGINEERING FOR THE LIGHT POLES AND
 FIXTURES. THE ENGINEERING NEEDS TO REFERENCE THE ACTUAL
 FIXTURE TYPE OR MODEL WITH ITS EPA AND ALSO VERIFY THE
 EXISTING FOOTER AND POLE ARE STRUCTURALLY ADEQUATE. FBC
 1609.1
  
 PROVIDE SPECIFICATIONS AND LISTING FOR NEW LIGHT POLES
 AND FIXTURES. NEC 90.70
  
 VERIFY THE EQUIPMENT GROUNDING CONDUCTOR FOR THE SITE
 LIGHTING HAS BEEN PROPORTIONATELY INCREASED IN SIZE
 ACCORDING TO THE CIRCULAR MIL AREA OF THE UNGROUNDED
 CONDUCTORS. ALTERNATELY PROVIDE FULL SIZE EQUIPMENT
 GROUNDING CONDUCTORS. NEC 250.4(A) (5), 250.122
  
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
 561-373-3701