| Plan Review Notes For Permit 14080632 |
| Permit Number |
14080632 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-03 11:20:49 | 14080632 | | | 500 BELVEDERE ROAD. | | | CANOPY AND SITE LIGHTING | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | PROVIDE AN ELECTRICAL RISER PLAN OF THE ELECTRICAL | | | SERVICE SHOWING LOCATION OF ALL METERS AND MAIN | | | DISCONNECTS. VERIFY THE ELECTRICAL SERVICE MAINS | | | SERVING THIS BUILDING ARE SIX OR LESS AND GROUPED IN | | | ONE LOCATION. VERIFY THE FAULT CURRENT RATING OF THE | | | NEW EQUIPMENT IS SUITABLE. NOTE THAT THE PLANS SHOW THE | | | LIGHTING PANELS AS BEING EXISTING ON ONE SHEET AND NEW | | | ON ANOTHER. NEC 110.9, 110.10, 110.26, 215.5, 230.71, | | | 240.24(D) | | | | | | PROVIDE WIND LOAD ENGINEERING FOR THE LIGHT POLES AND | | | FIXTURES. THE ENGINEERING NEEDS TO REFERENCE THE ACTUAL | | | FIXTURE TYPE OR MODEL WITH ITS EPA AND ALSO VERIFY THE | | | EXISTING FOOTER AND POLE ARE STRUCTURALLY ADEQUATE. FBC | | | 1609.1 | | | | | | PROVIDE SPECIFICATIONS AND LISTING FOR NEW LIGHT POLES | | | AND FIXTURES. NEC 90.70 | | | | | | VERIFY THE EQUIPMENT GROUNDING CONDUCTOR FOR THE SITE | | | LIGHTING HAS BEEN PROPORTIONATELY INCREASED IN SIZE | | | ACCORDING TO THE CIRCULAR MIL AREA OF THE UNGROUNDED | | | CONDUCTORS. ALTERNATELY PROVIDE FULL SIZE EQUIPMENT | | | GROUNDING CONDUCTORS. NEC 250.4(A) (5), 250.122 | | | | | | | | | ROBERT LECKY, CBO | | | ELECTRICAL PLANS REVIEW | | | 561-373-3701 | | | [email protected] | | | |
|