| Plan Review Notes For Permit 14080631 |
| Permit Number |
14080631 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-10-11 07:09:29 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) PRODUCT APPROVALS OR ENGINEERED DRAWINGS DETAILING | | | THE FASTENING OF THE CURB TO THE ROOF AND THE UNIT TO | | | THE CURB IS REQUIRED. FBCR M1307.2.1 THE ENGINEERED | | | CURB DETAIL DRAWING IS REQUIRED TO BE SIGNED, SEALED | | | AND DATED BY THE ENGINEER WHOSE NAME APPEARS IN THE | | | TITLE BLOCK. FS 471 | | | | | | 2) THE ENGINEERED CURB DETAIL DRAWING SPECIFIES A | | | CONCRETE ROOF DECK. THE PLANS THAT WERE SUBMITTED | | | INDICATE A WOOD ROOF DECK WITH WOOD FRAMING. PLEASE | | | REVISE DRAWING. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|