Date |
Text |
2014-08-18 11:07:41 | PERMIT # 14080614 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| BE SUBMITTED BY EMAIL ([email protected]) |
| ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND |
| APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT |
| 500 NORTH DIXIE HIGHWAY. |
| |
| ENTRY DOORS: THUMB-TURN LOCKS TO BE EQUIPPED WITH A |
| LOCK/UNLOCK INDICATOR. |
| |
| EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH |
| SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL |
| OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN |
| HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE |
| SPACED NOT MORE THAN 15 FEET ON CENTER. |
| |
| PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN |
| STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE |
| MAINTAINED AT ALL TIMES. |
| |
| AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY |
| EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL |
| EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED |
| WITH RESPECT TO THEIR DUTIES UNDER THE PLAN. |
| |
| EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED |
| IN THE USE OF PORTABLE FIRE EXTINGUISHERS. |
| |
| SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE |
| FIRE ALARM AND SPRINKLER SYSTEM. |
| |
| WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT |
| SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED |
| AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE |
| MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM |
| SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD |
| INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY |
| BE NEEDED. |
| |
| SUE ELLEN CALDERON |
| FIRE INSPECTOR & INVESTIGATOR |
| OFFICE OF THE FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| [email protected] |
| (561) 804-4751 |
| |