Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-08-15 09:47:11THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 DUE TO THE REMODELING AN EVALUATION OF THE FIRE ALARM
 AND FIRE SPRINKLER SYSTEM IS REQUIRED TO ENSURE CODE
 COVERAGE AND COMPLIANCE.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 FOR THE NEW REMODELED SPACES, PLEASE ENSURE THAT THE
 EMERGENCY LIGHTING FOR THE EXIT PATHS ARE ADJUSTED AS
 INDICATED ON THE PLAN.